9
the switch-on signal of the first thermostat. During this time, the valves
open and then the pump connected to the socket starts. The delay
is especially recommended if the zone valves are opened/closed by
slow-acting electrothermal actuators, because their opening/closing
time is approx. 4 min. If the socket output is already switched on,
the Turn on delay function will not be activated when the additional
thermostats switch on.
The active state of the Turn on delay function is indicated by the
green LED flashing with 3-second intervals.
If the „
MANUAL
” button is pressed while the Turn on delay is active
(green LED flashes with 3-second intervals), the LED stops flashing
and indicates the current operating mode (Automatic/Manual).
Press the „
MANUAL
” button again to change the working mode.
After 10 seconds, the green LED continues to flash with 3-second
intervals until the delay stops.