8

Attention!

 When reset, both the Off and On delays return to the off 

state.

4. DELAY OF THE OUTPUT

When designing heating zones - in order to protect the pumps - it is 

advisable to keep at least one heating circuit that is not closed by 

a zone valve (e.g. bathroom circuit). If this is not made, in order to 

prevent the heating system from an event in which all heating circuits 

are closed but a pump is switched on, the socket has two types of 

delay function.

Turn on delay

In turned on state, if the output of the socket is switched off, in order 

to open the valve(s) of the given heating circuit before starting the 

pump, the socket output switches on after a delay of 4 minutes from 

Содержание Q1RX

Страница 1: ...COMPUTHERM Q1RX Wireless Radio Frequency Thermostat Controlled Socket Operating Instructions...

Страница 2: ......

Страница 3: ...rating on 230 V e g fan heaters pumps zone valves etc Easy installation and operation no assembly required In response to the ON command of COMPUTHERM Q3RF Q5RF Q7RF and Q8RF wireless thermostats a su...

Страница 4: ...cation of the socket you should remember that bulky metal objects e g a boiler buffer tank etc and metal building structures may have an adverse effect on propagation of radio waves If it is possible...

Страница 5: ...ying the socket can cause electric shock or product failure Plug the COMPUTHERM Q1RX device into a power socket near the location of the device to be controlled A few seconds after the LED lights of t...

Страница 6: ...they can operate simultaneously ATTENTION The socket can be paired with up to 12 separate COMPUTHERM wireless thermostats at the same time If you do not want a particular thermostat to control the soc...

Страница 7: ...o pair more than 1 thermostat with the socket then repeat the previous steps with the other thermostats too If you have reached the maximum 12 synchronizable product limit then the red and green LEDs...

Страница 8: ...ne valve e g bathroom circuit If this is not made in order to prevent the heating system from an event in which all heating circuits are closed but a pump is switched on the socket has two types of de...

Страница 9: ...Turn on delay function will not be activated when the additional thermostats switch on The active state of the Turn on delay function is indicated by the green LED flashing with 3 second intervals If...

Страница 10: ...ded if the zone valves are opened closed by quick acting motorized actuators as their opening closing time is only a few seconds Activating the function in this case ensures that the heating circuits...

Страница 11: ...een LED shows the Turn on delay status while the red LED shows the Turn off delay status The function is activated when the corresponding LED is lit To save the settings and return to the default stat...

Страница 12: ...appears and disappears alternately on the display If you want to use the Q1RX socket with a wireless COMPUTHERM room thermostat that does not have a TEST button first press the and buttons to set the...

Страница 13: ...onnected to the socket can only be turned on and off manually without any temperature inspection The continuously illuminated green LED indicates MANUAL mode Pressing the ON OFF button switches on or...

Страница 14: ...14 Warning Themanufacturerdoesnotassumeresponsibility for any direct or indirect damages and loss of income occurring while the appliance is being used...

Страница 15: ...50 Hz Loadability 16 A 4 A inductive load Operating frequency 868 35 MHz Duration of activable Delay on function 4 minutes Duration of activable Delay off function 6 minutes Protection against enviro...

Страница 16: ...ments of directives RED 2014 53 EU and ROHS 2011 65 EU Copyright 2021 Quantrax Ltd All rights reserved Manufacturer QUANTRAX Ltd H 6726 Szeged F lem le u 34 Telephone 36 62 424 133 Fax 36 62 424 672 E...