INS_RL1000GW_REV– 15 Jul 2016 PAGE 86
INSTALLATION AND OPERATION MANUAL
RL1000GW
TECH SUPPORT: 1.888.678.9427
Command
Description
Create | update
Slot : 1 (constant)
Port : port number .1-2
Baud rate :
50,75,100,110,134,150,200,300,600,1200,2400,4800,9600,19200,38400,57600,115200,230400,4
60800,921600
Parity : no, odd, even
Stopbits : 1,2
admin-status: up| done. Default= up.
Mode of operation:
transparent
bus-idle-time : number of total serial bits received over the local serial link to be considered as
a single message
allowed-latency: given in msec this value describe the network allowed latency. This value
affects the time to be allowed to delay before transmitting UDP|TCP packets. The higher the
value is the more serial frames can accumulate into a single UDP|TCP packets. Default value
is 10msec which corresponds to max 3 bytes of serial data to be packed at a single UDP|TCP
packet (with 9.6kbps rate)
Remove
Slot : 1 (constant)
Port : port number .1-2
Show
Local-end-point
Create
Slot : 1 (constant)
Port : port number .1-2
Service id: numeric value of serial service.
Position:
Master – point to multipoint
Slave – point to multipoint
Application :
Serial-tunnel (default)
Terminal-server
iec101-gw
modbus-gw
buffer mode:
byte (default)
frame
protocol :
any (default)
modbus_rtu
iec101
iec101-link-address: set the IEC 101 link address. Applicable when ‘application’=’ iec101-gw’
and ‘protocol’=’ iec101’. <0-65535>
iec101-link-address-len: set the IEC 101 link address length. Applicable when ‘application’=’
iec101-gw’ and ‘protocol’=’ iec101’. <1|2> bytes. Default is 2.
iec101-originator-address: set if the ‘originator’ i=field is included in the IEC 101 message. This
will reflect on the Cause Of Transmission being 1 byte or 2 byte size. If ‘present’, COT=2. If
‘none’, COT=1.
unit-id: set the IEC 101 unit ASDU address. Applicable when ‘application’=’ iec101-gw’ and
‘protocol’=’ iec101’. <0-65535>
unit-id-len: set the IEC 101 ASDU length. Applicable when ‘application’=’ iec101-gw’ and
‘protocol’=’ iec101’. <1|2> bytes. Default is 2.