INS_RL1000GW_REV– 15 Jul 2016 PAGE 106
INSTALLATION AND OPERATION MANUAL
RL1000GW
TECH SUPPORT: 1.888.678.9427
Gateway 101/104 Configuration Flow
When attending a setup configuration, follow these below steps.
1. Ethernet connectivity towards the IEC 104 Client (SCADA)
a. Set service vlan and assign relevant ports.
b. Set ACE IP interface with the service vlan
c. Set static or dynamic routing if needed to reach the IEC 104 Client.
d. Verify by following methods
i. Successful ping between the IEC 104 Client (SCADA) and the RL1000GW designated IP
interface.
ii. IEC 104 connection established. Use the command “iec101-gw show all” to verify
connection at the switch.
2. Serial connection towards the locally connected IEC101 server (RTU)
a. Configure a serial port
i. Serial properties as baudrate, parity and such, must be consistent with those of the RTU.
ii. The serial port must be configured with ‘mode-of-operation set to ‘transparent’.
b. Configure a local service (serial local-end-point)
i. Create a local-end-point and assign the serial port.
ii. The local-end-point field ‘application’ must be set to ‘iec101-gw’
c. Enable the gateway
i. Assign the gateway to use the predefined ACE interface.
ii. Set the desired mode ‘balanced’ or ‘unbalanced’.
d. Configure the gateway with the RTU IEC101 properties. Key values are advised here
i. Common Address of ASDU value (CLI field ‘asdu_addr’). As set at the RTU.
ii. Common Address of ASDU length in bytes (CLI field ‘common_address_field_length’). As
set at the RTU.
iii. Link Address (CLI field ‘link_addr’). As set at the RTU.
iv. Link Address length in bytes (CLI field ‘link_address_field_length’). As set at the RTU.
v. Cause of Transmission length in bytes, determined by the usage of the originator address
field in the protocol. (CLI field ‘orig_addr_participate’)
vi. Connect the IEC101 server (RTU) to the serial port with a proper serial cable. Pin-out of
the RS232 RJ45 port of the switch is given in this manual. Control lines are not supported