background image

S E T U P   A N D   O P E R A T I O N   M A N U A L  

Page 2 

Purpose and Applicability 

The purpose of this document is to detail the operation instructions for the Matrix 1RU High Power DC Distribution Center. This 
document applies to Comm/net part number 

016-131-10 r01

 and 

r02

 with firmware version 

v2.0

Unpacking and Inspection 

The Matrix panel was carefully packaged at the factory to withstand the normal rigors of shipping. However, you should carefully 
inspect the box and contents to confirm that no damage occurred in transit. Most shipping carriers require notification of shipping 
damage within twenty-four hours of delivery, and it is the responsibility of the recipient to inspect the shipment immediately upon 
receipt. 

Contents 

 

 

 

Reversible Rack-Mount Ears for 19” or 23” Racks 

 

 

 

Rear Cover 

 

Breaker Extraction Tool 

 

 

If you ordered a compliment of breakers along with your panel, 
they will also be packaged along with the panel: 

 

 

 

 

Содержание Matrix 016-131-10

Страница 1: ...Matrix 1RU High Power Density DC Distribution Center SETUP AND OPERATION MANUAL S E T U P A N D O P E R A T I O N M A N U A L...

Страница 2: ...ed at the factory to withstand the normal rigors of shipping However you should carefully inspect the box and contents to confirm that no damage occurred in transit Most shipping carriers require noti...

Страница 3: ...rack use the two holes further back on the sides of the panel 2 Install the chassis ground cable A chassis ground cable should be landed on the two studs marked Chassis Ground on the left side of the...

Страница 4: ...on corresponding to the output channel to be fed viewing the front of the panel from left to right the positions are A1 A2 A3 A4 A5 A6 A7 A8 then B1 B2 B3 B4 B5 B6 B7 B8 Push until the circuit breaker...

Страница 5: ...ory Button The Breaker Inventory Button when held for more than five seconds is used to store the breaker inventory in nonvolatile memory The button may also be used to temporarily silence indefinitel...

Страница 6: ...is turned off the red Breaker Trip LED will turn on and the alarm beeper will sound When the breaker is turned back on the LED will turn off and the alarm beeper will silence 4 The breaker inventory...

Страница 7: ...successful Panel and Breaker Rating Limitations The panel is rated for a maximum current of 300A per bus The sum of the eight distribution breakers on either side of the panel may not exceed 300A The...

Страница 8: ...ine Breakers Each slimline breaker has two threaded brass screw hole features designed for extraction The breaker extraction tool is fitted with screw features designed to attach to the breaker Attach...

Страница 9: ...sory controller LED status indicator only About Comm net Systems Comm net Systems Inc CSI is the leader in high power density communications power systems Comm net offers comprehensive power and commu...

Отзывы: