9
13. Recommendations
Protect the cable against external damage by using, for example, a mechanical shield (tube, mesh, etc.).
Align the two parts correctly so that the polar plate is centered with the suction pad. The polar plate is
equipped with a flexible system, it can be slightly compressed to guarantee a good contact.
14. Periodic Inspection
This product should be checked periodically at least once a year. To do this, simply execute a procedure
and record the results on a form. The following points must be checked:
Example of an assembly on a door:
Version E or R
•
Remove magnetic hold (pin 8): E = +24V, R = aloft
• Move the transmitter 8 mm
•
SM1: Observe that the LED turns off
•
Check that contacts 1-5 and 4-6 are open
•
Check that contact 3 is closed (supply voltage)
• Approach the transmitter at 4 mm
•
SM1: Observe that the LED lights up
•
Check that contacts 1-5 and 4-6 are closed
•
Check that contact 3 is open (no voltage)
• Close door
•
Reactivate the hold (pin 8): E = aloft, R = +24V
EOP or ROP version
•
Remove magnetic hold (pin 8): E = +24V, R = aloft
• Move the transmitter 8 mm
•
SM1: Observe that the LED turns off
•
Check that contacts 1-5 and 4-6 are open
•
Check that contact 3 is closed (supply voltage)
• Approach the transmitter at 4 mm
•
SM1: Observe that the LED lights up
•
Check that contacts 1-5 and 4-6 are open
•
Check that contact 3 is open (no voltage)
• Close door
•
Reactivate the hold (pin 8): E = aloft, R = +24V
•
Check that contacts 1-5 and 4-6 are closed
•
Check that contact 3 is open (no voltage)
SM1 AND SM2 SERIES
Hold and interlock
9