COMITRONIC-BTI SM1 Series Скачать руководство пользователя страница 4

3 . Principle

3.1 keeping the doors in the closed position (machine) or in the open position (fire)

The electromagnetic lock acts as a safety sensor with a controllable hold using an electric control. 

We have the advantage of offering both types of interlock, in off or on position. This product is used in 

cases where the door can be subjected to shocks and vibrations to prevent it from triggering the safety.  

Versions are adapted to interlocking.

3.2 Interlocking

For safety interlocking applications, we offer "OP" versions that add compliance with ISO 14119. In this 

case, the use of the sticking with off power version is recommended. The holding force makes it possible 

to protect the operator during the stopping phase of an inertial movement whose duration is less than 

two seconds. The guaranteed force is called FZh.

4. Operation of OP versions

4.1 EOP version: interlocking with power off

4

- Door closed and locked

Open request, closed door

Door open

EOP

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

open

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

closed

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

open

- Door closed and locked

Open request, closed door

Door open

ROP

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

open

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

open

1

5

4

6

3

24 VDC

2

7

LATCH

8

0V +24V

contact

closed

4.2 ROP version: interlocking with power on

• 

Upon opening request (pin 8 powered), the safety contacts open

• 

The diagnostic contact (pin 3) reproduces the status of the door: sends the voltage if the door 

opens, regardless of the opening command

• 

The EOP version is recommended for machine safety because it preserves safety in case of 

power failure

• 

Upon opening request (pin 8 deactivated), the safety contacts open

• 

The diagnostic contact (pin 3) reproduces the status of the door: sends the voltage if the door 

opens, regardless of the opening command

• 

The ROP version can be used for machine safety according to the risk analysis

SM1 AND SM2 SERIES

Hold and interlock

Содержание SM1 Series

Страница 1: ...RS OF DANGEROUS MACHINES new generation Made in France SIL 2 CAT 3 Pld contacts 2A 48V 2 million operations at full load 3 year guarantee INNOVATION IS OUR DRIVING FORCE ADAPTABILITY IS OUR CULTURE CO...

Страница 2: ..._______________________________ 6 Summary of applications_________________________________________________ 7 Main Features__________________________________________________________ 8 Assembly Instruct...

Страница 3: ...sion R sticking with power on fire EOP version sticking with power off and compatible with ISO 14119 machine ROP version sticking with power on and compatible with ISO 14119 machine Stainless steel 31...

Страница 4: ...f 4 Door closed and locked Open request closed door Door open EOP 1 5 4 6 3 24 VDC 2 7 LATCH 8 0V 24V contact open 1 5 4 6 3 24 VDC 2 7 LATCH 8 0V 24V contact closed 1 5 4 6 3 24 VDC 2 7 LATCH 8 0V 24...

Страница 5: ...cations by model Door closed and locked Open request closed door Door open R 1 5 4 6 3 24 VDC 2 7 LATCH 8 0V 24V contact open 1 5 4 6 3 24 VDC 2 7 LATCH 8 0V 24V contact closed 1 5 4 6 3 24 VDC 2 7 LA...

Страница 6: ...i baseplate Stainless steel 316L PUR polyether Weight with packaging 1110 g 700 g 2000 g Screw mounting 2 x M4 2 x M4 2 x M6 7 Main Features 6 8 Assembly Instructions 8 1 SM1 PL and SM1 OX a Drill the...

Страница 7: ...ld and interlock 144 117 2 6 39 S c r e w c o v e r 11 EPB handle dimensions optional item M8 for handle attachment center distance 117 mm PL OX 82 5 72 R 50 31 5 6 1 5 20 5 3 2 F4 3 Antibacterial han...

Страница 8: ...26XXL monitoring on off management B22 CV 1OL RGO D3T10 BU MKT opening command SPEEDTRONIC zero speed control FKT 5 m 10 m or 15 m connection FKT cord Brown Blue White Pink Yellow Gray Green Red 1 5 4...

Страница 9: ...t the LED turns off Check that contacts 1 5 and 4 6 are open Check that contact 3 is closed supply voltage Approach the transmitter at 4 mm SM1 Observe that the LED lights up Check that contacts 1 5 a...