 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: 

Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: 

Space size  20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

__________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

______________ Btu/Hr

Gas water heater*

______________ Btu/Hr

Gas furnace

______________ Btu/Hr

Vented gas heater

______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances* +

______________ Btu/Hr

Total                            =

______________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200  Btu/Hr (maximum the space can support)

54,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Continued

Example:

Gas water heater

44,000

Btu/Hr

Vent-free heater   +

10,000

Btu/Hr

Total                     =

54,000

Btu/Hr

Содержание CGP10LA

Страница 1: ...and service must be performed by a qualified installer service agency or the gas supplier WARNING Thisisanunvented gas firedheater Itusesair oxy gen from the room in which it is installed Provisions f...

Страница 2: ...n Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in the...

Страница 3: ...ional Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any s...

Страница 4: ...ntilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the...

Страница 5: ...fuel burning appliances in the space Vent free heater ______________ Btu Hr Gas water heater ______________ Btu Hr Gas furnace ______________ Btu Hr Vented gas heater ______________ Btu Hr Gas firepl...

Страница 6: ...23 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controll...

Страница 7: ...See Accessory page 16 LOCATING HEATER This heater is designed to be mounted on a wall WARNING Maintainthemini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ances from floor ceiling and jo...

Страница 8: ...igure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place large ope...

Страница 9: ...rom Installation must include an equipment shutoffvalve groundjointunion andplugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 13 Pr...

Страница 10: ...ply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Applymixtureofliquidsoapandwaterto gas joints Bu...

Страница 11: ...ystem If control knob does not pop up when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in push down and release ignitor button This will light p...

Страница 12: ...ct pilot flame pat tern Figure 19 shows an incorrect pilot flame pattern The incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools...

Страница 13: ...ere is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when control knob is released REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if...

Страница 14: ...a few hours of operation 1 Turn control knob to LOW position and let warm up for a minute 2 Operate burner until air is removed from line Have gas checked by local propane LP gas company 3 Observe mi...

Страница 15: ...apors from paint hair spray glues etc See IMPORTANT statement above 2 Low fuel supply 3 Gas leak SeeWarning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot...

Страница 16: ...st Parts Central or call DESA International s Parts Department at 1 800 972 7879 for referral information When calling DESA International have ready model number of your heater the replacement part nu...

Страница 17: ...616 791 8270 www nbmc com Dayton Hardware P O Box 275 North Dayton Station Dayton OH 45404 0275 All States 937 258 3721 OH 1 800 762 3426 Halco Enterprises 208 Carter Drive Unit 21 West Chester PA 19...

Страница 18: ...18 104270 PROPANE LP GAS HEATER CGP10LA CGP6LA 12 2 12 1 ILLUSTRATED PARTS LIST 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Страница 19: ...1 11 098249 01 098249 01 Nut M5 2 12 099059 03 099059 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 02 104263 01 Burner 1 14 09...

Страница 20: ...apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by i...

Отзывы: