PROPANE/LP GAS HEATER

AIR FOR
COMBUSTION AND
VENTILATION

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

Confined Space

The information on pages 4 through 6 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 6.

If your home does not meet all of the
three criteria above, proceed 

Deter-

mining Fresh-Air Flow for Heater Lo-
cation, page 5.

Confined and Unconfined Space

The National Fuel Gas Code ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m

3

 per kw) of the aggre-

gate input rating of all appliances installed
in that space and an unconfined space as a
space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space. Rooms
communicating directly with the space in
which the appliances are installed*, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

Содержание CGP10LA

Страница 1: ...and service must be performed by a qualified installer service agency or the gas supplier WARNING Thisisanunvented gas firedheater Itusesair oxy gen from the room in which it is installed Provisions f...

Страница 2: ...n Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in the...

Страница 3: ...ional Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any s...

Страница 4: ...ntilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the...

Страница 5: ...fuel burning appliances in the space Vent free heater ______________ Btu Hr Gas water heater ______________ Btu Hr Gas furnace ______________ Btu Hr Vented gas heater ______________ Btu Hr Gas firepl...

Страница 6: ...23 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controll...

Страница 7: ...See Accessory page 16 LOCATING HEATER This heater is designed to be mounted on a wall WARNING Maintainthemini mumclearancesshowninFigure 4 Ifyoucan providegreaterclear ances from floor ceiling and jo...

Страница 8: ...igure 8 Tightening Anchors Thin or Thick Wall thick wall shown Solid Wall 1 16 Space Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place large ope...

Страница 9: ...rom Installation must include an equipment shutoffvalve groundjointunion andplugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 13 Pr...

Страница 10: ...ply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 15 Applymixtureofliquidsoapandwaterto gas joints Bu...

Страница 11: ...ystem If control knob does not pop up when released contact a qualified service person or gas supplier for repairs 6 With control knob pressed in push down and release ignitor button This will light p...

Страница 12: ...ct pilot flame pat tern Figure 19 shows an incorrect pilot flame pattern The incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools...

Страница 13: ...ere is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when control knob is released REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if...

Страница 14: ...a few hours of operation 1 Turn control knob to LOW position and let warm up for a minute 2 Operate burner until air is removed from line Have gas checked by local propane LP gas company 3 Observe mi...

Страница 15: ...apors from paint hair spray glues etc See IMPORTANT statement above 2 Low fuel supply 3 Gas leak SeeWarning statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot...

Страница 16: ...st Parts Central or call DESA International s Parts Department at 1 800 972 7879 for referral information When calling DESA International have ready model number of your heater the replacement part nu...

Страница 17: ...616 791 8270 www nbmc com Dayton Hardware P O Box 275 North Dayton Station Dayton OH 45404 0275 All States 937 258 3721 OH 1 800 762 3426 Halco Enterprises 208 Carter Drive Unit 21 West Chester PA 19...

Страница 18: ...18 104270 PROPANE LP GAS HEATER CGP10LA CGP6LA 12 2 12 1 ILLUSTRATED PARTS LIST 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Страница 19: ...1 11 098249 01 098249 01 Nut M5 2 12 099059 03 099059 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 02 104263 01 Burner 1 14 09...

Страница 20: ...apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by i...

Отзывы: