RECOMMENDED HEIGHT AND LENGTH
If the refrigerant piping is longer than the
recommended length, or if the height
difference between the indoor and outdoor
unit is greater than recommended, the
capacity will drop and the compressor could
malfunction. Select an installation location
that is within the recommended parameters.
(MAXIMUM PIPING LENGTH
& HEIGHT RECOMMENDED)
Piping length (feet)
Notes
Cooling
capacity
7,500 to
9,000
Btuh
Add
charge
Not
needed
Needed
(1)
Installation
not
recom-
mended
Unit
Piping
Diameter
1/4" and
3/8”
Recommended height difference is 23 ft or less
*Evacuate refrigerant lines
(1)
• Additional charge volume = (piping length - 23 ft.) x 0.2 oz.
An installation with a piping length of 23 ft. or less is desirable.
If this is not possible, the maximum piping length can be
extended to 50 ft. by charging the system with additional
refrigerant. However, cooling and heating capacity will be
reduced.
Piping length (feet)
Notes
Cooling
capacity
18,500 to
36,000
Btuh
Add
charge
Not
needed
Needed
(2)
Installation
not
recom-
mended
Unit
Piping
Diameter
Recommended height difference is 23 ft or less
(2)
• Additional charge volume = (piping length - 33 ft.) x 0.2 oz.
*Evacuate refrigerant lines
An installation with a piping length of 33 ft. or less is desirable.
If this is not possible, the maximum piping length can be
extended to 55 ft. by charging the system with additional
refrigerant. However, cooling and heating capacity will be
reduced.
INSTALLATION METHOD
HOLE DRILLING:
After deciding the
method your unit will be installed, a hole to
route the connecting tubes and wires to the
outdoor unit is to be drilled on the wall. The
hole must be lower than the point where the
drainpipe attaches to the drain pan of the
unit. It should also be slightly declined
towards the outside.
23
50
33
55
Содержание AMC 25
Страница 16: ...MODEL AMW 45 60 ...
Страница 21: ...AMW AMC 25 ...
Страница 22: ...AMW AMC 30 ...
Страница 23: ...AMW AMC 45 60 ...