Comelit ILS-2 Скачать руководство пользователя страница 7

 

 

3.1.6 USB Connector

 

 

The detector is equipped with a USB type B connector to allow connection to a PC via a US cable (not supplied). 
This communication port allows configuration of the sensor, and downloading of logged data using the VSC 
software. 
The connector is protected by a screw-fit cover and this must be re-fastened after every use, to prevent dust and 
dirt from settling on it. 

4 Installing the piping

 

 

Several standard configurations of the pipe network are illustrated below. 

 

T

The sizing software ASPIRE2 must be used to calculate the channelling time, dilution effects etc. for all the 

pipe networks required for individual applications. 
Use 25 mm red ABS piping with sampling holes drilled along its length. The piping will terminate with an end 
cap, with a hole drilled in its centre. The position of each sampling hole should adhere to guidelines for point 
smoke detectors. It is important to note that the concentration of smoke entering a single hole will be diluted 
by clean air from other sampling holes and from the end cap hole.

 

 

4.1 Piping specifications

 

 

In accordance with EN54-20 standards, the pipes must be red ABS and conform to EN 50086-1 
(Crushing 1, Impact 1, Temperature 31) with a nominal external diameter of 25 mm. The pipes are 
normally supplied in 3-metre lengths and cut as required, but linked using solvent welded sockets or 
connected with socket unions (inspectable).

 

 

IMPORTANT note: 

the ILS-2 pipe inlets are tapered so as to allow “push-fit” coupling of the piping coming 

from the site. The end of the inlet pipe must be cut cleanly so as to allow airtight 
coupling with the tapered inlet. The inlet piping junction with the tapered collector 
MUST NOT BE GLUED: doing so will invalidate the sensor warranty.

 

 

4.2 Fixing

 

 

The standard fixing method for piping requires special clips or clamps. The fixing spacing (distance between two 
adjacent clips) is typically 1.5 m.

 

 

4.3 Bends

 

 

 

 

 

 

 

 

 

 

Figure 4-1: 45° bend and 90° bend

 

 

The available bends are 90° and 45°. It is important to use 90° swept bends and not “sharp” ones, as sharp 
bends introduce high pressure losses and increase the channelling time for the sampling holes downstream of 
the bend.

 

Содержание ILS-2

Страница 1: ...1 ASPIRATING SMOKE DETECTOR 1 ZONE 2 DETECTORS ILS 2...

Страница 2: ...ed The following typographic conventions are used in this manual Convention Description Bold Used to indicate emphasis used for menu names menu options toolbar icons Italic Used to indicate links to o...

Страница 3: ...1 Piping specifications 7 4 2 Fixing 7 4 3 Bends 7 4 4 End caps 8 4 5 Sampling holes 8 4 6 Air outlet 8 4 7 Filters 8 4 8 Standard pipe configurations 9 5 Detectors 9 6 2 User functions 11 6 3 Setup n...

Страница 4: ...installed by authorised personnel in accordance with local and national regulations Remove the transparent cover using the keys provided and loosen the fasteners Use the template to position the fixin...

Страница 5: ...n the speed of the fan used for the application please refer to Table 11 2 Current Consumption vs Fan Speed 3 1 2 ACTION 2 ACTION 1 Relay output The voltage free contacts of the relay ACTION ACTION wi...

Страница 6: ...6 3 1 5 External Reset The application of a voltage of 24 Vdc to these terminals triggers a reset of all fault and alarm events present...

Страница 7: ...uted by clean air from other sampling holes and from the end cap hole 4 1 Piping specifications In accordance with EN54 20 standards the pipes must be red ABS and conform to EN 50086 1 Crushing 1 Impa...

Страница 8: ...bris through to the end of the pipe in the latter case you will need to fit the end cap afterwards In standard applications the sampling hole faces downwards 4 6 Air outlet The extracted air after bei...

Страница 9: ...y and the fan speed set to 9 maximum The use of bends as described in section 4 3 will have a minimal effect on performance e g response time Note the abovementioned values are based on EN54 20 certif...

Страница 10: ...SMOKE DETECTOR FAULT detector fault 1 per detector ISOLATE Disabled relays not active AIRFLOW OK HIGH AIRFLOW LOW AIRFLOW POWER ON Power supply present FAN FAULT Fan fault GENERAL FAULT General fault...

Страница 11: ...d one at a time e g press the CHANGE button six times to illuminate the number 5 LED on the display then press the SELECT button etc the CODE LED flashes during this procedure the Unlock LED will ligh...

Страница 12: ...Set the delay in FLOW HIGH and LOW LEDs 2 See table paragraph 6 3 3 indication of flash together FLOW FAULT Set ALERT threshold The ALERT LED flashes 3 Set threshold for The ACTION LED 5 ACTION flash...

Страница 13: ...13 sensors...

Страница 14: ...gue values from the TWO detectors exceed the relevant thresholds Notes Mode 3 is not permitted in installations which require VdS approval ILS 2 is supplied in standard mode 1 If required jointly the...

Страница 15: ...the calibrated reading for at least the duration of the flow fault indication delay see section 6 3 2 above For most installations especially if compliance with EN54 20 is required the default setting...

Страница 16: ...r cover This test electronically simulates the effect of smoke in the optical chamber 7 2 System Before checking the system as a whole make sure the top cover of the unit is in place As a minimum requ...

Страница 17: ...pipe so that the top surface of the filter is positioned flush with the pipe 5 Remove the point detector s from the mounting base by twisting them anti clockwise 6 Remove the detector cover by prying...

Страница 18: ...Class C Class B Class A 1 18 6 3 100 2 9 3 1 100 3 4 1 N A 100 4 1 N A N A 100 5 or higher N A N A N A N A Note table 9 1 shows the limit that should not be exceeded for the 3 sensitivity classes Fig...

Страница 19: ...cover is fitted properly and the enclosure is fully sealed Make sure the airflow calibration procedure has been carried out see section 6 2 Make sure the filter is in good condition see section 8 Flo...

Страница 20: ...length of pipes 100 m Protection rating IP65 with air outlet piping installed IP23 without Operating temperature range From 10 to 50 C Operating humidity From 10 to 95 RH non condensing Certifications...

Страница 21: ...21...

Отзывы: