Table 6-1: User functions for ILS-2
FUNCTION
DISPLAY
VALUE
NOTES
RECOMMENDE
D
Reset the unit
The RESET LED flashes
Press CHANGE to reset the
outputs
Isolate the relay outputs
The ISOLATE LED is lit
steadily
Press CHANGE to Isolate or
when the system is
Reset the outputs
isolated and flashes
when it is running
Adjust the speed
The POWER LED
5
The greater the assigned value,
of the fan (0 = min., 9 =
max.)
flashes
the shorter the response time
Adjust the sensitivity
The FLOW OK LED
5
Sensitivity = 9 (flow sensor
of the airflow (v. 6.3.3)
flashes
most sensitive)
Sensitivity = 2 (flow sensor
less sensitive)
Select the value of the
The FLOW HIGH LED
8
HIGH FLOW threshold
flashes
Select the value of the
The FLOW LOW LED
2
LOW FLOW threshold
flashes
DOWN
Set the delay in
FLOW HIGH and LOW
LEDs
2
See table, paragraph 6.3.3
indication of
flash together
FLOW FAULT
Set ALERT threshold
The ALERT LED flashes
3
Set threshold for
The ACTION LED
5
ACTION
flashes
Set FIRE threshold
The FIRE LED flashes
7
Select the mode of
One of the MODE LEDs
LED 1 ON = use only
detection
flashes
detector 1
LED OR ON = use only one
of the two detectors, the other is
for
backup
LED 1&2 ON = use
both detectors
Buzzer (buzzer)
The buzzer sounds
If the sounds emitted are
intermittently
long, the buzzer is active; if
the sounds are short it is not.
Set Autoreset or
The Laser fault LED
0 = Autoreset
Manual Reset
flashes
1 = Manual Reset
Calibrate flow
The FAN FAULT
Press and hold the CHANGE
button
sensors
LED flashes
for at least 2 seconds
The fan will stop temporarily
and restart
later.
Calibration is complete
when you see the
high and low flow LEDs, and an
LED among them indicating the
value
of the current flow across the