Comelit ILS-2 Скачать руководство пользователя страница 12

 

12 

 

 

Table 6-1: User functions for ILS-2

 

FUNCTION

 

DISPLAY

 

VALUE

 

NOTES

 

 

 

RECOMMENDE
D

 

 

Reset the unit

 

The RESET LED flashes

 

 

Press CHANGE to reset the

 

 

 

 

outputs

 

Isolate the relay outputs

 

The ISOLATE LED is lit 

steadily

 

 

Press CHANGE to Isolate or

 

 

when the system is

 

 

Reset the outputs

 

 

isolated and flashes

 

 

 

 

when it is running

 

 

 

Adjust the speed

 

The POWER LED

 

5

 

The greater the assigned value,

 

of the fan (0 = min., 9 = 
max.)

 

flashes

 

 

the shorter the response time

 

Adjust the sensitivity

 

The FLOW OK LED

 

5

 

Sensitivity = 9 (flow sensor

 

of the airflow (v. 6.3.3)

 

flashes

 

 

most sensitive)

 

 

 

 

Sensitivity = 2 (flow sensor

 

 

 

 

less sensitive)

 

Select the value of the

 

The FLOW HIGH LED

 

8

 

 

HIGH FLOW threshold

 

flashes

 

 

 

Select the value of the

 

The FLOW LOW LED

 

2

 

 

LOW FLOW threshold

 

flashes

 

 

 

DOWN

 

 

 

 

Set the delay in

 

FLOW HIGH and LOW 

LEDs

 

2

 

See table, paragraph 6.3.3

 

indication of

 

flash together

 

 

 

FLOW FAULT

 

 

 

 

Set ALERT threshold

 

The ALERT LED flashes

 

3

 

 

Set threshold for

 

The ACTION LED

 

5

 

 

ACTION

 

flashes

 

 

 

Set FIRE threshold

 

The FIRE LED flashes

 

7

 

 

Select the mode of

 

One of the MODE LEDs

 

 

LED 1 ON = use only

 

detection

 

flashes

 

 

detector 1

 

 

 

 

LED OR ON = use only one

 

 

 

 

of the two detectors, the other is 
for

 

 

 

 

backup

 

 

 

 

LED 1&2 ON = use

 

 

 

 

both detectors

 

Buzzer (buzzer)

 

The buzzer sounds 

 

 

If the sounds emitted are

 

 

intermittently

 

 

long, the buzzer is active; if

 

 

 

 

the sounds are short it is not.

 

Set Autoreset or

 

The Laser fault LED

 

 

0 = Autoreset

 

Manual Reset

 

flashes

 

 

1 = Manual Reset

 

Calibrate flow

 

The FAN FAULT

 

 

Press and hold the CHANGE 

button

 

sensors

 

LED flashes

 

 

for at least 2 seconds

 

 

 

 

The fan will stop temporarily

 

 

 

 

and restart

 

 

 

 

later.

 

 

 

 

Calibration is complete

 

 

 

 

when you see the

 

 

 

 

high and low flow LEDs, and an

 

 

 

 

LED among them indicating the 
value

 

 

 

 

of the current flow across the 

Содержание ILS-2

Страница 1: ...1 ASPIRATING SMOKE DETECTOR 1 ZONE 2 DETECTORS ILS 2...

Страница 2: ...ed The following typographic conventions are used in this manual Convention Description Bold Used to indicate emphasis used for menu names menu options toolbar icons Italic Used to indicate links to o...

Страница 3: ...1 Piping specifications 7 4 2 Fixing 7 4 3 Bends 7 4 4 End caps 8 4 5 Sampling holes 8 4 6 Air outlet 8 4 7 Filters 8 4 8 Standard pipe configurations 9 5 Detectors 9 6 2 User functions 11 6 3 Setup n...

Страница 4: ...installed by authorised personnel in accordance with local and national regulations Remove the transparent cover using the keys provided and loosen the fasteners Use the template to position the fixin...

Страница 5: ...n the speed of the fan used for the application please refer to Table 11 2 Current Consumption vs Fan Speed 3 1 2 ACTION 2 ACTION 1 Relay output The voltage free contacts of the relay ACTION ACTION wi...

Страница 6: ...6 3 1 5 External Reset The application of a voltage of 24 Vdc to these terminals triggers a reset of all fault and alarm events present...

Страница 7: ...uted by clean air from other sampling holes and from the end cap hole 4 1 Piping specifications In accordance with EN54 20 standards the pipes must be red ABS and conform to EN 50086 1 Crushing 1 Impa...

Страница 8: ...bris through to the end of the pipe in the latter case you will need to fit the end cap afterwards In standard applications the sampling hole faces downwards 4 6 Air outlet The extracted air after bei...

Страница 9: ...y and the fan speed set to 9 maximum The use of bends as described in section 4 3 will have a minimal effect on performance e g response time Note the abovementioned values are based on EN54 20 certif...

Страница 10: ...SMOKE DETECTOR FAULT detector fault 1 per detector ISOLATE Disabled relays not active AIRFLOW OK HIGH AIRFLOW LOW AIRFLOW POWER ON Power supply present FAN FAULT Fan fault GENERAL FAULT General fault...

Страница 11: ...d one at a time e g press the CHANGE button six times to illuminate the number 5 LED on the display then press the SELECT button etc the CODE LED flashes during this procedure the Unlock LED will ligh...

Страница 12: ...Set the delay in FLOW HIGH and LOW LEDs 2 See table paragraph 6 3 3 indication of flash together FLOW FAULT Set ALERT threshold The ALERT LED flashes 3 Set threshold for The ACTION LED 5 ACTION flash...

Страница 13: ...13 sensors...

Страница 14: ...gue values from the TWO detectors exceed the relevant thresholds Notes Mode 3 is not permitted in installations which require VdS approval ILS 2 is supplied in standard mode 1 If required jointly the...

Страница 15: ...the calibrated reading for at least the duration of the flow fault indication delay see section 6 3 2 above For most installations especially if compliance with EN54 20 is required the default setting...

Страница 16: ...r cover This test electronically simulates the effect of smoke in the optical chamber 7 2 System Before checking the system as a whole make sure the top cover of the unit is in place As a minimum requ...

Страница 17: ...pipe so that the top surface of the filter is positioned flush with the pipe 5 Remove the point detector s from the mounting base by twisting them anti clockwise 6 Remove the detector cover by prying...

Страница 18: ...Class C Class B Class A 1 18 6 3 100 2 9 3 1 100 3 4 1 N A 100 4 1 N A N A 100 5 or higher N A N A N A N A Note table 9 1 shows the limit that should not be exceeded for the 3 sensitivity classes Fig...

Страница 19: ...cover is fitted properly and the enclosure is fully sealed Make sure the airflow calibration procedure has been carried out see section 6 2 Make sure the filter is in good condition see section 8 Flo...

Страница 20: ...length of pipes 100 m Protection rating IP65 with air outlet piping installed IP23 without Operating temperature range From 10 to 50 C Operating humidity From 10 to 95 RH non condensing Certifications...

Страница 21: ...21...

Отзывы: