AF10‐E Control Connector
5
Tech Support: 1‐818‐841‐5500
Blast Control:
Pin 1 provides 115VAC power from the AccuFlo. The host must provide a switch to put this
voltage back in to Pin 2, which will cause the blaster to blast. When Pin 2 is left floating, the blaster will not
blast. 200mA of current is typical.
PE:
Pin 4 provides an optional bonding path to Primary Earth through the AccuFlo. If the host is otherwise
bonded to PE, do not use this pin.
Regulator Control:
The regulator must be powered by 24vdc through Pin 7 and ground through Pin 6. The
regulator requires 60mA of current. The blast pressure is set by providing a 0‐10vdc signal at Pin 8, which
corresponds to a pressure of 0‐148psi. The internal resistance of the regulator’s input is 100ohms minimum.
AF10‐E Cables and Controllers
Cabling and control depends on how the user desires to control the AF10‐E. Use the above table to
determine which cable to use. If the AF10‐E is paired with an AutoFill unit, refer to the AutoFill manual for
additional wiring information.