InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-36
Block By AR
[ENABLED / DISABLED]
If enabled, the synchro-check will not evaluate synchronous state until the AC Reclosing output is
activated after the trip termination.
ENABLED:
The binary output will activate only after the AC Reclosing output is activated
DISABLED: The binary output activates regardless of the state of the AC Reclosing output
Default setting: DISABLED
Dead V Lim
[%Un]
Threshold for evaluating the mains or bus voltage as "dead".
Step:
0,1 % of nominal voltage
Range:
0,0 - 50,0 %
Default setting: 20,0 %
Dead T Del
[s]
If the mains or bus voltage stays under the Dead V Lim threshold for longer than tis time, the voltage
is considered as "dead".
Step:
0,1 s
Range:
0,0 - 150,0 s
Default setting: 5,0 s
SynC Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for synchro check protection.
Default setting: None
N
OTE
:
In case of setting to None, the sync check function has no influence on trip outputs. If any trip output is
selected, then deactivation of that trip output is blocked while the synchronous conditions are not
evaluated. When the synchronous conditions are met, the deactivation of the trip output is no longer
blocked.
AC Reclosing
AR Delay [s]
Delay for activating the AC Reclosing binary output after fault reset.
Step:
0,01 s
Range:
0,00 - 600,00 s
Default setting: 10,00 s
Rec Initiate
[Common / Trp 1 / Trp 2]
Selection of which output is considered as a trigger for the AC reclosing function. Deactivation of this
output initiates the counter of AR Delay for reconnecting by the AC Reclosing output.
Common:
the output Comm Trp is considered the trigger for AC reclosing counter
Trp 1:
the output Trp 1 is considered the trigger for AC reclosing counter
Trp 2:
the output Trp 2 is considered the trigger for AC reclosing counter
Default setting: Common
Pole Slip
Gear Teeth
[-]
Number of teeth on the engine's (generator's) flywheel for the pick-up sensor
Step:
1 [-]
Range:
1 - 500