InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-47
Input resistance
4,2 kOhm
Binary outputs
Number of binary outputs
8
Galvanic insulation
Not insulated
Type
Transistor, switching to negative supply terminal
Operating voltage
8-36VDC
Switching current
500mA (suppression diodes required for inductive loads)
Analog inputs
Number of analog inputs
3
Galvanic insulation
Not insulated
Electrical range
0-2500ohm
Resolution
10bits, 4digits
Supported sensor types
Predefined: VDO 10Bar, VDO Temperature, VDO Fuel level
User defined: 10 points non-linear sensors can be defined by the
user
Precision
1% from the range
Mains measurements
Measurement inputs
3ph mains voltage, 3ph mains current
Measurement type
True RMS
Voltage range
480V Ph-Ph (277V Ph-N)
Max. measured voltage
340V Ph-N
Voltage accuracy
1% of nominal voltage
at 20°C and 50 or 60 Hz;; 1,5% on the
complete frequency and temperature range
Current range
5A
Max. measured current
9A
Max. allowed current
12A continuous, 50A/1s
Current accuracy
2% of nominal current at CT Ratio = 50A / 5A or higher
CT input burden
<0.5VA
Frequency range
30-70Hz, measured from L3
Frequency accuracy
0.05Hz
C
AUTION
!
To assure accurate measurement of the mains current, we recommend direct metallic connection
between COM terminal of Mains Current measurement and the minus "-" terminal of the unit power
supply. The potential difference between those two points must not overreach 10 V.
NVD and Sync Check measurement
Measurement inputs
NVD voltage, Sync Check
Measurement type
True RMS
Voltage range
NVD: 277V
Sync Check: 480 V