InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-25
Dyn Volt
V Lim 1, V Lim 2, V Lim 3
[% Un]
Voltage limits determining the Dyn Volt Prot curve.
Step:
1 %Un
Range:
0 - 100 %Un
Default setting:
- V Lim 1
30%Un
- V Lim 2
70%Un
- V Lim 3
90%Un
Delay 1, Delay 2, Delay 3
[s]
Time delays determining the Dyn Volt Prot curve.
Step:
0,01 s
Range:
0,01
–
10,00 s
Default setting:
- Delay 1
0,15 s
- Delay 2
0,70 s
- Delay 3
1,50 s
Reset Time
[s]
Time delay after which the protection starts to follow the curve from the beginning.
Step: 0,01 s
Range: 0,00..10,00 s
Default setting: 2,00 s
DynVoltTrpBO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for Dynamic Voltage protection.
Default setting: None
QU
V<
[%Un]
Threshold for voltage measurement
Step:
1 %Un
Range:
80
–
90 %Un
Default setting: 85 %Un
Rst V<
[%Un]
Threshold for voltage measurement hysteresis
Step:
1 %Un
Range:
90
–
100 %Un
Default setting: 95 %Un
I Min
[%In]
Threshold for current measurement
Step:
1 %In
Range:
2
–
20 %In