Mounting 

 

1.  Turn off the power at the circuit breaker or fuse. 
2.  Carefully position all wires so that there is room for the wall box for the dimmer. 
3.  Mount the dimmer into the box with the supplied mounting screws. 
4.  Attach the wallplate. 
5.  Complete the installation by restoring power at the circuit breaker or fuse. 

 
Data Connection

 

 

Fixtures on a serial data link must be daisy chained in one single line.  To comply with the EIA-485 
standard, no more than 32 fixtures should be connected on one data link.  Connecting more than 32
fixtures on one serial data link without the use of a DATA optically-isolated splitter may result in 
deterioration of the digital DMX signal. 

 

 

 

 

 

 

Maximum recommended serial data link distance: 500 m (1640 ft) 
Maximum recommended number of fixtures on a serial data link: 32

 

DMX Data Cable 
 
If installer prefers 3-wire data cables, we suggest a Belden

©

 9481 or equivalent cable which 

meets the specifications for EIA RS-485 applications (Use PCL002 DMX hardwiring DMX 
coupler).  Standard microphone cables cannot transmit Color Ray signal reliably over long 
distances.  The cable must have the following characteristics: 
 

 

Type: 

    shielded, 

2-conductor 

twisted 

pair 

 

 

Maximum capacitance between conductors: 

 

 

 

 

 

 

 

 

30 pF/ft 

 

 

Maximum capacitance between conductor and shield: 

 

 

 

 

 

 

 

55 pF/ft 

  Maximum 

resistance: 

   20 

ohms/1000 

ft 

 

 

Normal impedance: 

 

 

 

100

140 ohms 

 

If installer prefers a RJ45/CAT5 Data installation, a RJ45 jack can be used (use PCL004 
RJ45 coupler). 
 
Notice: To comply with all local codes and jurisdiction, qualified communications technicians 
must do communications wiring. 
 
Notice: Communication cables and AC power lines must not be run in the same conduit. 
 

A.  Route Data Cables in series between housing and any communications accessories 

using DATA IN and DATA OUT. 

B.  In order that they may be easily accessed from the room once construction is 

complete, secure data cables in the immediate proximity of the housings. 

 
Coloronix strongly recommends clearly marking communication cables in such a way to 
indicate the correct order of connection. 
 

C.  Use RJ45 DMX terminator, insert in “DATA OUT” of last fixture in series. 
 

*To avoid signal transmission problems and interference, it is always advisable to connect to a 
DMX signal terminator.

 

Page 9—Coloronix Color Ray Manual V1.0 

Содержание Color Ray

Страница 1: ...COLOR RAY REMOTE CONTROL DEVICE Coloronix Inc 5461 West Jefferson Boulevard Los Angeles California 90016 323 677 4242 http www rgbw com Page 1 Coloronix Color Ray Manual V1 0...

Страница 2: ...e found in this manual Coloronix Inc 5461 West Jefferson Boulevard Los Angeles California 90016 Tech Support 909 RGBW 555 http www rgbw com Coloronix and the Coloronix logo are brands of Coloronix Inc...

Страница 3: ...on Key 5 Specifications 5 Planning for Installation 6 Unpacking 6 Preparation 6 Points to Consider About Data 6 Color Ray Stand Alone Mode 7 Electrical Connection 8 Mounting 9 Data Connection 9 Troubl...

Страница 4: ...ote Control at peak performance This manual must be complimented by additional references consultation from qualified professional s and observance of state and local codes and regulations This rule a...

Страница 5: ...rious injury or death WARNING Not following instructions or safety labels may result in property damage or serious injury WARNING Modifying servicing or ignoring these safety indications may void the...

Страница 6: ...damage claims Please recycle or appropriately discard of any packing materials Preparation Before Installation Coloronix suggests Consulting the provided submittal drawings to recognize layouts of lum...

Страница 7: ...ue Dark Blue Sky Blue Repeat 5 minutes p 4 Cool Blue Dark Blue Sky Blue Repeat 30 minutes p 2 Exotic Colors Orange Turquoise Neon Green Fuchsia Repeat 0 5 seconds p 2 Exotic Colors Orange Turquoise Ne...

Страница 8: ...in the wall box 2 Connect CAT5 RJ45 Cable to Receiver Coupler 3 Connect Power Connect the line voltage 120V wires in the following manner Screw the wire nuts clockwise so that no bare conductors show...

Страница 9: ...smit Color Ray signal reliably over long distances The cable must have the following characteristics Type shielded 2 conductor twisted pair Maximum capacitance between conductors 30 pF ft Maximum capa...

Страница 10: ...device is operating at less than 25Hz Further Troubleshooting Should problems occur while using the product unplug it at once and contact Coloronix Inc Tech Support 909 RGBW 555 support coloronix com...

Страница 11: ...Corrosion or discoloration in components or products are not covered Except as written above no other warranties are applicable Coloronix Inc is not liable for any damages accidental unusual or resul...

Отзывы: