3 Operation Modes and Functions
3.3.1
Auto mode function requirement
TS range is 62 ~88 17 ~30
When T1<TS-1, select the setting temperature of
TS-1 for Heating operation’s temperature.
When TS+2≥T1≥TS-1,select the Fan-only mode.
When T1>TS+2, select the setting temperature(TS )
for Cooling operation’s temperature.
The indoor fan motor operates at Auto-fan mode with
speed uncontrolled and not changed.
3.3.2 Fan-only mode function requirement
The compressor and outdoor fan are OFF at Fan-
only mode (except P1 protection).
The speed of indoor fan can be optionally chosen as High/Mid/Low.
The TS can’t be controlled because of the LED displaying as T1.
The ION/TIMER functions are valid at the fan-only mode.
3.3.3 Cooling mode function requirement
The speed of indoor fan can be optionally selected as High/Mid/Low.
The outdoor fan will be turned on as soon as the unit being on
cooling mode.The operation of outdoor fan is according to the
compare of T1 and TS when the water level is below to switch 1.
If not, the outdoor fan doesn’t work.
The compressor operates as below:
Operation conditon
(T1-Ts)
℃
Compressor on
+1
0
Compressor off
a)
If T1 TS+1 , outdoor fan
operates. After 15 seconds,
compressor operates.
b)
The compressor is on, if
T1≤TS, this compressor will
stop. If outdoor fan operates for
3 minutes at least, it will stop
for a delay for 5 seconds.