3.

 

3 Operation Modes and Functions  

  

3.3.1

 

Auto mode function requirement  

 

 TS range is 62  ~88   17  ~30

 

 

When T1<TS-1, select the setting temperature of 

TS-1 for Heating operation’s temperature.

 

 When TS+2≥T1≥TS-1,select the Fan-only mode.

 

 

 When T1>TS+2, select the setting temperature(TS ) 

for Cooling operation’s temperature.

 

 

The indoor fan motor operates at Auto-fan mode with 

speed uncontrolled and not changed.

 

 

3.3.2 Fan-only mode function requirement

 

 

 The compressor and outdoor fan are OFF at Fan-

only mode (except P1 protection).

 

 The speed of indoor fan can be optionally chosen as High/Mid/Low.

 

 

 The TS can’t be controlled because of the LED displaying as T1. 
 The ION/TIMER functions are valid at the fan-only mode.

 

 

3.3.3 Cooling mode function requirement

 

 

 The speed of indoor fan can be optionally selected as High/Mid/Low.

 

 

 The outdoor fan will be turned on as soon as the unit being on 

cooling mode.The operation of outdoor fan is according to the 
compare of T1 and TS when the water level is below to switch 1.

 

 

If not, the outdoor fan doesn’t work. 

 The compressor operates as below:

 

 

Operation conditon

 

 

(T1-Ts)

 

Compressor on

 

 

 
 

+1

 

 

 

0

 

 

Compressor off

 

 

a)

 

If T1 TS+1 , outdoor fan 

operates. After 15 seconds, 
compressor operates.  
b)

 

The compressor is on, if 

T1≤TS, this compressor will 
stop. If outdoor fan operates for 
3 minutes at least, it will stop 
for a delay for 5 seconds.  

Содержание MPPD-12CRN1

Страница 1: ...COLDWAVE Portable Air Conditioner Model MPPD 12CRN1 12000 BTU h 110V 1Ph 60Hz R410A...

Страница 2: ...Features 4 Speed Fan Ion Generator Sleep Mode Timer Auto Cool Dry Mode Swing Function Follow Me Temperature Sensor Swing Button LED Display Note Cooling Only No heat function...

Страница 3: ...1 DIMENSION H W D Unit Dimension W H D mm inch Single hose 454 17 9 700 27 6 365 14 4 small body Single hose 467 18 4 765 30 1 397 15 6 Double hose 467 18 4 765 30 1 478 18 8...

Страница 4: ...tor is energized and will help to remove pollen and impur ities from the air and trap them in the filter Press it for 3 seconds again to stop the ION feature UP AND DOWN BUTTON 4 Used to adjust increa...

Страница 5: ...llow Me Temp Sensing feature point the remote control towards the unit and press the Follow Me Temp Sensing button The remote display is actual temperature at its location The remote control will send...

Страница 6: ...TO mode you can not select the fan speed TIMER OPERATION When the unit is on press the Timer button will initiate the Auto off stop program the TIMER OFF indicator light illuminates Press the UP or do...

Страница 7: ...mode 3 ELECTRONIC FUNCTION 3 1 Abbreviation T1 Indoor room temperature T2 Temperature of evaporator T3 Temperature of condenser TS The setting temperature S1 Water level swicth 3 2 Main Protection 3 2...

Страница 8: ...0 6 27 9 1245 129 2 54 2 959 33 8 1 33 3269 82 4 28 8 7198 131 55 2 8442 35 6 2 31 5635 84 2 29 8 3357 132 8 56 2 7382 37 4 3 29 9058 86 30 7 9708 134 6 57 2 6368 39 2 4 28 3459 87 8 31 7 6241 136 4 5...

Страница 9: ...igh Mid Low The TS can t be controlled because of the LED displaying as T1 The ION TIMER functions are valid at the fan only mode 3 3 3 Cooling mode function requirement The speed of indoor fan can be...

Страница 10: ...working And outdoor fan will stop for a delay of 5 seconds b When T1 59 15 outdoor fan operates and compressor will restart operation after 15seconds The speed can t be controlled at drying mode and i...

Страница 11: ...TIMER functions are valid at the heating mode 3 4 6 Heating mode function requirement for Heat Pump TS range is 62 88 17 30 T1 TS 41 5 compressor operates T142 8 6 41 5 T1 42 8 6 86 30 86 30 100 4 38...

Страница 12: ...122 50...

Страница 13: ...vaporator temperature sensor error E3 Condenser temperature sensor error Causation a Port of temperature sensor is loose b Temperature sensor is bad c Circuit component is bad Solution a Check the con...

Страница 14: ...f it can not resume after 2 minutes please replace the PCB 4 2 Protection code and Solution P1 Water full protection Causation Water in tank is full Solution Connect the drain hose and drain the colle...

Страница 15: ...move the heat sources if possible c Connect the duct and make sure it can function properly d Decrease the TS e Clean the air filter Noisy or vibration Causation The ground is not level or not flat en...

Страница 16: ...5 INTERNAL STRUCTURE Temperature sensor Evaporator Centrifugal fan Compressor Water pump Indoor fan motor Capacitor of compressor Condenser Water level sensor...

Страница 17: ...Display board Temperature sensor Display board Water level switch Relay Louver motor Outdoor motor Indoor motor Power on off Capacitor of fan motor Electronic control box...

Страница 18: ...ly 1 5 Horizontal louver 6 Cover of electronic control box 1 6 Bracket 7 Suction pipe assembly 1 7 Gear wheel 8 Discharge pipe assembly 1 7 Gear wheel 10 Capillary assembly 1 8 Louver motor 11 Evapora...

Страница 19: ...fugal fan 27 7 Bracket of water level sensor 32 6 Power cord 27 8 Micro switch 33 Capacitor box 27 9 Bracket of Micro switch 34 Capacitor of compressor 27 10 Dobber case 35 Fasten board of Capacitor 2...

Страница 20: ...2 8 Capacitor box 27 17 Top cover of Shaded pole motor 3 Dobber 27 18 Bottom cover of Shaded pole motor 5 Electronic control box assembly 27 19 Drain Connector 5 1 Electronic control box 27 20 Connec...

Страница 21: ...Servair Limited 45 Market Street Marabella Trinidad Tel 1 868 658 1911 1 868 658 1910 1 868 658 2010 Fax 1 868 658 3012 Email paul servair com...

Отзывы: