16
6 Messages and Error Indications
The following displays are shown when an error occurs or a hardware change is detected.
Table 4. Error/Faults conditions
Error/Faults
Conditions
Upper display
Lower
Display
(where fitted)
Configuration & Setup is required. Seen at first turn on or if
hardware configuration changed.
Press
to enter Configuration Mode,
next press
or
to enter the unlock code number,
then press
to proceed.
Configuration must be completed before return to operator
mode is allowed
1
Goto
Conf
Loop alarm set for
Auto
but
Pb_P
is set to 0.0% (on/off
control). Loop Alarm uses the manual Loop Alarm Time un-
til PID control is restored. Ensure that
lat.
is set correctly.
aerr
laen
PV Input more than 5% over-range
2
[HH]
*
Normal Display
PV Input more than 5% under-range
3
[LL]
*
Normal Display
Sensor Break. Break detected in the input sensor or wiring
oPeN
*
Normal Display
Auxiliary input over-range
Normal Display
[HH]
*
Auxiliary input under-range
Normal Display
[LL]
*
Auxiliary Break. Break detected in the auxiliary input
Normal Display
oPeN
*
Option 1 module fault.
err
**
oPn1
Option 2 module fault.
err
**
oPn2
Option 3 module fault.
err
**
oPn3
Option A module fault.
err
**
oPna
Option B module fault.
err
**
oPnb
*Note: Input sensor and Auxiliary over/under-range or break indications will be seen wherever these values would normally be
displayed.
1
This feature does not guarantee correct configuration. It only helps to ensure that the unit will be configured be-
fore use. Use of set-up mode is not enforced but may be essential for the users application.
2
If the PV display exceeds
9999
before 5% over-range is reached, an over-range indication is given.
3
Indicators will allow up to 10% under-range on non-zero based Linear ranges. If the PV display is less than
-1999
before the % under-range is reached, an under-range indication is given.