Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
/
CLVR04Z / CLVR08Z / CLVR12Z
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
42
7.3.3 Manual call point Alarm threshold setting at the uSwitch.
The switch with number 5 allows modification of the Manual call point threshold.
uSwitch
CONFIGURATION
DESCRIPTION
Manual call point threshold at 8 V.
(Default Control panel setting)
Manual call point threshold at 12 V
7.3.4 Last Zone operation mode setting at the uSwitch
The switch with number 6 allows changing the operation of the Last Zone of the Control Panel
(example: zone 8 of the CLVR08Z). This Last Zone can work as a normal detection zone or for
the monitoring of a fire warning external device.
In this last case, using a serial resistance of 470
Ω
with the fire warning external device, gives
indication of Open line fault at the Last Zone of the Control panel instead of an alarm (see
example in the wiring diagram of chapter 5.2).
uSwitch
CONFIGURATION
DESCRIPTION
Last Zone in Standard Fire detection Mode.
►
Detector Alarm is indicated as Detector Alarm.
►
Manual call point Alarm is indicated as Manual call point Alarm.
(Default Control Panel setting)
Last Zone in Fault signaling Mode.
►
Detector Alarm is indicated as Open line Fault.
►
Manual call point Alarm is indicated as Open line Fault.