29
KEY
LED
COLOUR
DESCRIPTION
Red
Fire alarm due to activation of manual call point or detector.
►
Fixed
Green
System operating through 110~230 V/AC power supply.
►
Fixed
Green
System operating under batteries.
►
Fixed
Amber
System fault
►
Fixed
Amber
General power supply fault.
►
Fixed
Fault 110~230V/AC input, batteries input, 30V
output, etc
Amber
General sounder output condition
►
Fixed
Relay triggered
►
Intermittent
Fault in the relay, line open, line crossed,
sounder fuse etc.
Amber
Condition of fault output
►
Fixed
Relay triggered
►
Intermittent
Fault in relay, line open, line crossed, fuse
fault etc.
Amber
Fault in the auxiliary battery supply
►
fixed
Batteries faulty, discharged or missing.
►
Intermittent
Fault in the battery charger.
Amber
CPU fault
►
Fixed
Control Panel not operating.
Amber
Control Panel communication through RS485 port
►
Intermittent
Control panel communicating
Amber
Level of access to keyboard of Control Panel.
►
Off
Level 1.
►
Fixed
Level 2.
►
Intermittent
Level 3.
Amber
Silence sounders
►
Fixed
General relay sounder in silent position.
Amber
Disable delays of panel
►
Fixed
Control panel operating without delays at the
general sounder outputs, fault and extinction relay “R2”.
Amber
Zone out of service.
►
Fixed
At least 1 zone out of service.
Amber
Zone in test mode
►
Fixed
At least 1 zone in test mode.
Red
Alarm in zone indicated.
►
Fixed
activated by manual call point
►
Intermittent
activated by Detector
Amber
Fault in zone indicated.
►
Fixed
Open line fault.
►
Intermittent
Crossed line fault.
Amber
Zone indicated in test or disabled
►
Fixed
Zone disabled.
►
Intermittent
Zone in test.
A
ALARM
Red
Power Supply
B
Bateria / Battery
C
Avería General
General Fault
D
Av. Alimentación
Supply Fault
E
Relé Sirena
Sounder Relay
F
Relé Avería
Fault Relay
G
Avería Batería
Battery Fault
H
Avería CPU
CPU Fault
I
J
COM
Acceso Teclado
Keyboard Access
K
sin Retardo
no delay
M
desconexión
general disable
N
modo pruebas
test mode
O
1
ALARM
P
AVERÍA / FAULT
PRUEBA / ANULADO
TEST / DISABLED
Q
R
L
1