background image

5

12. PRESSURE SENSOR CALIBRATION

In case of wrong lecture of the pressure sensor it can be adjusted 

again. 

For the pressure sensor calibration is necessary to have a pressure 

gauge in the installation. Proceed following next steps:

ZERO REGULATION

1.  Open the taps living the hydraulic net without pressure.
2.  Press simultaneously the buttons   and   until the display 

show 0.0 flashing.

3.  Press     to validate. 

FULL SCALE

1.  Start the pump and close all the taps to pressuri-

ze the installation and reach the cut-out pressure. 

 

(If the pump does not start, please hold the button    to 

reach the cut-out pressure)

2.  Press simultaneously the buttons    and   till the display 

flashes with a figure.

3.  Adjust the pressure with the arrows push-buttons until the va-

lue on the display maches with the pressure reading.

4.  Press     to validate. 

Remark 5: pressure sensor decalibration should not be a nor-

mal event. If it is frequently repeated contact the technical 

service.  

13. REGISTER OPERATION DATA AND ALARMS 

 +   +   

- Press simultaneously  +   +   during 5 seconds.

- Press   to advance in the REGISTER.

- The DATA sequence is:

MESSAGE

DESCRIPTION

SCOPE

rEC
HF xxx

Controller operating hours

0-65535

HP xxx

Pump operating hours

0-65535

CF xxx

Operating cycles

Number of start-stop cycles.

0-999999

Cr xxx

Number of connections to the 

power supply.

0-65535

A01 xxx

Number of A01 alarms.

0-999

A02 xxx

Number of A02 alarms.

0-999

A04 xxx

Number of A04 alarms.

0-999

A05 xxx

Number of A05 alarms.

0-999

A11 xxx

Number of A11 alarms.

0-999

APM xxx

Number of over-pressure 

alarms (---).

0-999

rPM x.x

Maximum registered pressure.

rSt

ENTER   -> EXIT.

+   -> All the alarms are 

restored except the opera-

tion data.

14. WARNINGS AND ALARMS

COD.

DESCRIPTION

SYSTEM REACTION

A01

O

DRY-RUN-

NING

(Only for 

SWITCHMA-

TIC 2)

When is detected a dry-run operation 

the pump is automatically stopped. By 

mean of ENTER the normal operation 

can be manually restored.

((O))

After the activation of the dry-running 

alarm if the Automatic system reset 

(ART) is enabled, a first attempt at 5 

minutes and then an attempt every 30 

minutes for 24 hours is performed in 

order to restore the normal operation. 

This alarm can also be reset manually 

with the ENTER push-button. If the 

alarm persists after 24 h we find a 

definitive alarm. 

A11

O

DRY-RUN-

NING 

(BY MINIMUM 

PRESSURE)

Is displayed during normal operation 

if the pressure is below the minimum 

pressure (Px.x) - previously set - during 

a period (txx) - also previously set - in 

the ADVANCED MENU.

If at any time the pressure exceeds the 

minimum pressure, the operation is 

restored automatically and the alarm 

is cleared.

Normal operation can also be restored 

manually by pressing ENTER.

A21

((O))

DRY-RUN-

NING 

(BY EXTERNAL 

LEVEL INPUT)

Only if tE1 has been activated in the 

advanced programming menu.

The alarm is displayed on the screen 

when the float switch detects a low 

level of water in the suction tank, 

stopping the operation of the pump. It 

is automatically restored when there is 

water again.

A02

OVERLOAD

(Only SW2)

Overcurrent alarm is activated when the 

nominal pump current is exceeded. 

4 automatic reset attempts prior to the 

final alarm are performed.

During the attempts display will show 

current.

Normal operation can also be restored 

manually by pressing ENTER.

((O))

A04

(((O)))

FAST CYCLING

(Hammering)

This alarm can be unabled or activated 

in the BASIC MENU.  The alarm is 

activated when 3 consecutive cycles 

occur in a range lower than the set time 

(between cycle and cycle). 

If it has been activated rc1, this alarm 

does not stop the normal operation but 

are added 5 seconds to the start delay 

in order to protect the electric pump.

If it has been activated rc2, the pump 

is stopped.

To RESET the normal operation press 

ENTER.

A05

O

DAMAGED 

PRESSURE 

TRANSMITTER

CONTACT WITH YOUR SUPPLIER.

15. EC STAMENT OF COMPLIANCE 

COELBO CONTROL SYSTEM, S.L. States, on our own responsibi-

lity, that all materials here with related comply with the following 

European Directives:
 

- 2014/35/EU.

 

- 2014/30/EU.

 

- 2011/65/EU+2015/863/EU. 

Name: 

 

- SWITCHMATIC 1 /1+

 

- SWITCHMATIC 2/2+

 

- SWITCHMATIC 3/

3+

 

Standards : EN-60730-2-6, EN-60730-1, EN-61000-6-1, EN-61000-

6-3, IEC-60730-1, IEC-60730-2-6

F. Roldán Cazorla   

Director Técnico

04/05/2016

COELBO CONTROL SYSTEM, S.L.

Ctr de Rubí, 288 - P.I. Can Guitard

08228 Terrassa - BARCELONA (SPAIN)

16. CLASSIFICATION AND TYPE

According to IEC 60730-1  and EN 60730-1 this unit is a control 

sensor device, electronic, independent assembly, programming 

type A with action type 1B (microdisconnection). Operating value: I 

<20% I learned. Pollution degree 2 (clean environment). Rated im-

pulse voltage: cat II / 2500V. Temperatures for ball test: enclousure 

(75) and PCB (125). 

Содержание SWITCHMATIC 1

Страница 1: ...HMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus PROGRAMMATION AVANC E Risque de dommage au groupe de pression et ou l installation Risque de choc lectrique Risque pour les objets et ou les p...

Страница 2: ...ssion d arr t 1 8 bar version plus 12 bar Diff rentiel maximal 7 5 bar version plus 11 5 bar Diff rentiel SW 0 5 bar SW2 synchro 1 bar Configuration usine marche arr t 3 4 bar Raccordement r seau hydr...

Страница 3: ...elle est d tect rc2 2 1 r 01 r 99 Uniquement si l tape pr c dente l alarme de cycles rapides rc1 rc2 a t activ e alors nous pouvons s lectionner la dur e en secondes du p riode entre trois cons cutive...

Страница 4: ...1 10 H00 H99 R glage de la minuterie d inondation La pompe s arr te si le temps pr c demment configur en minutes de fonctionnement ininterrompu est d pass D connect H00 1 minute H01 99 minutes H99 H00...

Страница 5: ...DE PRESSION MINIMALE Appara t si en fonctionnement normal la ipression est inf rieure la pression minimale Px x pr d finie pendant la dur e txx pr alablement d fini dans le MENU AVANC Si tout moment...

Страница 6: ...6 1x48 230Vac Vdc...

Страница 7: ...V CLASSEMENT DES CONTACTS Tension de commutation maximale 230VAC 220VDC Puissance de commutation maximale 62 5VA 30W OUT SCH MA B ALIMENTATION LECTRIQUE ET MOTEUR 1x48 230Vac Vdc SW3 1x110 230Vac SW1...

Страница 8: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMME D...

Страница 9: ...MATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus CONFIGURAZIONE AVANZATA Rischio di danno al gruppo di pressione o all impianto Rischio di scossa elettricha Rischio per le persone e o per gli...

Страница 10: ...50 C Temperatura ambiente massima 60 C Pressione di messa in marcia 0 5 7 bar v plus 11 bar Pressione di fermata 1 8 bar v plus 12 bar Differenziale mass Pstop Pstart 7 5 bar v plus 11 5 bar Differen...

Страница 11: ...eggia e il led START ON Mediante i tasti e si aggiusta la pressione di avvio da 0 5 a 7 bar version 11 bar Premere per validare 4 Inserire pressione d arresto Premere durante 3 secondi Visualizziamo n...

Страница 12: ...terno disattiva la pompa il display visualizza EL tE0 9 1 co1 co0 Solo nel caso di tE1 attivato co1 nc contatto normalmente chiuso co0 no contatto normalmente aperto 10 H00 H99 Impostazione del timer...

Страница 13: ...a definitiva A11 O MANCANZA D ACQUA PER PRESSIONE MINIMA Appare se in funzionamento nor male la pressione per sotto della pressione minima Px x previamente impostata durante il tempo txx previamente i...

Страница 14: ...6 1x48 230Vac Vdc DIAGRAMMA A INDIVIDUALE GRUPPO SOLO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3...

Страница 15: ...1 C2 30mA L U N V CONTATTI RATING Mass tensione di commutazione 230VAC 220 VDC Mass potenza di commutazione 62 5VA 30W OUT SCHEMA B ALIMENTAZIONE E MOTORE 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Premi...

Страница 16: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMMA D DIMENSIONI...

Страница 17: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus Riesgo para personas y o objetos Riesgo por choque el ctrico Riesgo de da o al grupo de presi n o a la instalaci n AJUSTES AVANZADOS...

Страница 18: ...IP55 Temperatura m xima del agua 50 C Temperatura ambiente m xima 60 C Presi n de puesta en marcha 0 5 7 bar v plus 11 bar Presi n de de paro 1 8 bar v plus 12 bar Diferencial m xim Pstop Pstart 7 5...

Страница 19: ...do y se ilumina el led START Mediante las teclas y se ajustar la presi n de puesta en marcha de 0 5 a 7 bar version 11 bar Pulsar para validar 4 Introducir presi n de paro Pulsar durante 3 segundos Vi...

Страница 20: ...0 H99 Configuraci n del temporizador contra inundaci n Se detiene la bomba si se supera el tiempo en minutos previamente configurado de funcionamiento inin terrumpido Desconectado H00 1 minuto H01 99...

Страница 21: ...R PRESI N M NIMA Aparece si en funcionamiento normal la presi n est por debajo de la presi n m ni ma Px x previamente establecida durante el tiempo txx previamente establecido en el MEN AVANZADO Si en...

Страница 22: ...6 1x48 230Vac Vdc DIAGRAMA A INDIVIDUAL GRUPAL S LO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 USO OBLIGATORIO DE TANQUE HIDRONEUM TICO...

Страница 23: ...SW1 2 SW3 SW1 2 SW3 C1 C2 C1 C2 30mA 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 L U N V Presione para liberar Cables 2 max 1 5 mm 2 min 0 2 mm CLASIFICACI N DE CONTACTOS Max Voltaje de conmutaci n 230VAC...

Страница 24: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMA D DIMENSIONES...

Страница 25: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus ADVANCED SETTINGS Risk of damaging the pressure assemblies and or the plant Risk by electric shock Risk for people and or objects...

Страница 26: ...11 5 bar Minimum diff Pstop Pstart SW 0 5 bar SW2 synchro 1 bar Factory setting start stop 3 4 bar Hydraulic inlet G1 4 Fem NPT 1 4 Fem Net weight without cables 0 3 kg 5 HYDRAULIC INSTALLATION diagra...

Страница 27: ...d on screen LED START lights up and display is flashing By mean of and is adjusted the start pressure from 0 5 to 7 bar version 11 bar Press for validation 4 Set the cut out stop pressure Press during...

Страница 28: ...tivates the equipment the display shows EL tE0 9 1 co1 co0 Only in case of tE1 activated co1 nc normally closed contact co0 no normally open contact co1 10 H00 H99 Anti flooding configuration If activ...

Страница 29: ...s after 24 h we find a definitive alarm A11 O DRY RUN NING BY MINIMUM PRESSURE Is displayed during normal operation if the pressure is below the minimum pressure Px x previously set during a period tx...

Страница 30: ...6 1x48 230Vac Vdc DIAGRAM A INDIVIDUAL SYSTEM ONLY SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK...

Страница 31: ...W3 C1 C2 C1 C2 30mA L U N V CONTACTS RATING Max switching voltage 230VAC 220 VDC Max switching power 62 5VA 30W OUT DIAGRAM B POWER SUPPLY AND MOTOR 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Press to rel...

Страница 32: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAM D DIMENSIONS...

Отзывы: