background image

3

P-BUT-

TON

TOUCH

ACTION

click!

From state ON

: unit OFF.

From state OFF

: the pump starts and 

keeps operating until reaching Pstop.

From any configuration MENU

: the 

parameter value is accepted.

HOLD 

DOWN

From state ON

: unit OFF.

From state OFF

: the pump starts and 

keeps operating until the push-button 

is released.

click!

Pstart is displayed on the screen for 3 

seconds.

3”

Pstart adjustment mode.

click!

Pstop is displayed on the screen for 3 

seconds.

3”

Pstop adjustment mode.

click!

Is displayed on the screen instantaneous 

current consumption. 

If it is already displayed then we switch 

to instantaneous pressure view.

3”

Rated current adjustment.

8. STARTUP (diagram C)

 

Before starting the device please read the previous sections, 

especially “Hydraulic Installation” and “Electrical connec-

tion”.

Follow next steps:

1. Only for type SW2 set the pump rated current intensity value.

- Press    during 3 seconds.

- The current intensity value is displayed on screen, LED A 

lights up and display is flashing. 

- By mean of   and 

 is adjusted the rated current reflected 

in the characteristics plate of the motor. See Note 1.

- Press   for validation.

2. Start the device by pressing  .

3. Set the cut-in (start) pressure:

- Press    during 3 seconds.

- The start pressure value is displayed on screen, LED START 

lights up and display is flashing.  

- By mean of   and   is adjusted the start pressure from 0,5 

to 7 bar (+ version=11 bar).

- Press   for validation.

4. Set the cut-out (stop) pressure:

-  Press   during 3 seconds.

-  The stop pressure value is displayed on screen, LED STOP 

lights up and display is flashing.  

- By mean of   and   is adjusted the stop pressure from 1 to 

8 bar (+ version=12 bar).

- Press   for validation.

5. The unit is ready to operate but more optional adjustments can 

be set through basic and advanced MENUS. See the next chapter. 

Remark 1: it is important to introduce exactly the rated 

current specified on the nameplate of the pump.

9. BASIC MENU 

  +   

(diagram C)

- Press simultaneously   +   during 5 seconds.
- By mean of   or   the values can be changed.
- Press   for validation.

- The parameters sequence is:

it

TYPE

SYSTEM REACTION

FACTORY 

SETTING

1 BAR P We can select the pressure units 

displayed beetween bar and psi. 

bar

2 rc0 rc2

Fast-cycling alarm:

- rc0: alarm unabled.

- rc1: activated, when hammering is 

detected it is delayed the start 

in order to protect the pump.

- rc2: alarm is activated and the 

pump is stopped upon detec-

tion.

rc2

2.1 r.01 r.99

Only if fast-cycling alarm has been 

activated in the previous step 

(rc1&rc2). It can be choosed the 

maximum time period between 3 

consecutive starts that will be con-

sidered fast cycling (between 1 sec. 

and 99 sec.)

3 seconds

3 Sb0 Sb1

Stand-by mode activated (Sb1), for 

low power consumption, or unabled 

(Sb0).

Sb0

Содержание SWITCHMATIC 1

Страница 1: ...HMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus PROGRAMMATION AVANC E Risque de dommage au groupe de pression et ou l installation Risque de choc lectrique Risque pour les objets et ou les p...

Страница 2: ...ssion d arr t 1 8 bar version plus 12 bar Diff rentiel maximal 7 5 bar version plus 11 5 bar Diff rentiel SW 0 5 bar SW2 synchro 1 bar Configuration usine marche arr t 3 4 bar Raccordement r seau hydr...

Страница 3: ...elle est d tect rc2 2 1 r 01 r 99 Uniquement si l tape pr c dente l alarme de cycles rapides rc1 rc2 a t activ e alors nous pouvons s lectionner la dur e en secondes du p riode entre trois cons cutive...

Страница 4: ...1 10 H00 H99 R glage de la minuterie d inondation La pompe s arr te si le temps pr c demment configur en minutes de fonctionnement ininterrompu est d pass D connect H00 1 minute H01 99 minutes H99 H00...

Страница 5: ...DE PRESSION MINIMALE Appara t si en fonctionnement normal la ipression est inf rieure la pression minimale Px x pr d finie pendant la dur e txx pr alablement d fini dans le MENU AVANC Si tout moment...

Страница 6: ...6 1x48 230Vac Vdc...

Страница 7: ...V CLASSEMENT DES CONTACTS Tension de commutation maximale 230VAC 220VDC Puissance de commutation maximale 62 5VA 30W OUT SCH MA B ALIMENTATION LECTRIQUE ET MOTEUR 1x48 230Vac Vdc SW3 1x110 230Vac SW1...

Страница 8: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMME D...

Страница 9: ...MATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus CONFIGURAZIONE AVANZATA Rischio di danno al gruppo di pressione o all impianto Rischio di scossa elettricha Rischio per le persone e o per gli...

Страница 10: ...50 C Temperatura ambiente massima 60 C Pressione di messa in marcia 0 5 7 bar v plus 11 bar Pressione di fermata 1 8 bar v plus 12 bar Differenziale mass Pstop Pstart 7 5 bar v plus 11 5 bar Differen...

Страница 11: ...eggia e il led START ON Mediante i tasti e si aggiusta la pressione di avvio da 0 5 a 7 bar version 11 bar Premere per validare 4 Inserire pressione d arresto Premere durante 3 secondi Visualizziamo n...

Страница 12: ...terno disattiva la pompa il display visualizza EL tE0 9 1 co1 co0 Solo nel caso di tE1 attivato co1 nc contatto normalmente chiuso co0 no contatto normalmente aperto 10 H00 H99 Impostazione del timer...

Страница 13: ...a definitiva A11 O MANCANZA D ACQUA PER PRESSIONE MINIMA Appare se in funzionamento nor male la pressione per sotto della pressione minima Px x previamente impostata durante il tempo txx previamente i...

Страница 14: ...6 1x48 230Vac Vdc DIAGRAMMA A INDIVIDUALE GRUPPO SOLO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3...

Страница 15: ...1 C2 30mA L U N V CONTATTI RATING Mass tensione di commutazione 230VAC 220 VDC Mass potenza di commutazione 62 5VA 30W OUT SCHEMA B ALIMENTAZIONE E MOTORE 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Premi...

Страница 16: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMMA D DIMENSIONI...

Страница 17: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus Riesgo para personas y o objetos Riesgo por choque el ctrico Riesgo de da o al grupo de presi n o a la instalaci n AJUSTES AVANZADOS...

Страница 18: ...IP55 Temperatura m xima del agua 50 C Temperatura ambiente m xima 60 C Presi n de puesta en marcha 0 5 7 bar v plus 11 bar Presi n de de paro 1 8 bar v plus 12 bar Diferencial m xim Pstop Pstart 7 5...

Страница 19: ...do y se ilumina el led START Mediante las teclas y se ajustar la presi n de puesta en marcha de 0 5 a 7 bar version 11 bar Pulsar para validar 4 Introducir presi n de paro Pulsar durante 3 segundos Vi...

Страница 20: ...0 H99 Configuraci n del temporizador contra inundaci n Se detiene la bomba si se supera el tiempo en minutos previamente configurado de funcionamiento inin terrumpido Desconectado H00 1 minuto H01 99...

Страница 21: ...R PRESI N M NIMA Aparece si en funcionamiento normal la presi n est por debajo de la presi n m ni ma Px x previamente establecida durante el tiempo txx previamente establecido en el MEN AVANZADO Si en...

Страница 22: ...6 1x48 230Vac Vdc DIAGRAMA A INDIVIDUAL GRUPAL S LO SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 USO OBLIGATORIO DE TANQUE HIDRONEUM TICO...

Страница 23: ...SW1 2 SW3 SW1 2 SW3 C1 C2 C1 C2 30mA 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 L U N V Presione para liberar Cables 2 max 1 5 mm 2 min 0 2 mm CLASIFICACI N DE CONTACTOS Max Voltaje de conmutaci n 230VAC...

Страница 24: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAMA D DIMENSIONES...

Страница 25: ...1 SWITCHMATIC 1 1 plus SWITCHMATIC 2 2 plus SWITCHMATIC 3 3 plus ADVANCED SETTINGS Risk of damaging the pressure assemblies and or the plant Risk by electric shock Risk for people and or objects...

Страница 26: ...11 5 bar Minimum diff Pstop Pstart SW 0 5 bar SW2 synchro 1 bar Factory setting start stop 3 4 bar Hydraulic inlet G1 4 Fem NPT 1 4 Fem Net weight without cables 0 3 kg 5 HYDRAULIC INSTALLATION diagra...

Страница 27: ...d on screen LED START lights up and display is flashing By mean of and is adjusted the start pressure from 0 5 to 7 bar version 11 bar Press for validation 4 Set the cut out stop pressure Press during...

Страница 28: ...tivates the equipment the display shows EL tE0 9 1 co1 co0 Only in case of tE1 activated co1 nc normally closed contact co0 no normally open contact co1 10 H00 H99 Anti flooding configuration If activ...

Страница 29: ...s after 24 h we find a definitive alarm A11 O DRY RUN NING BY MINIMUM PRESSURE Is displayed during normal operation if the pressure is below the minimum pressure Px x previously set during a period tx...

Страница 30: ...6 1x48 230Vac Vdc DIAGRAM A INDIVIDUAL SYSTEM ONLY SW2 SWITCHMATIC 1 2 SWITCHMATIC 3 MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK MANDATORY USE OF PRESSURE TANK...

Страница 31: ...W3 C1 C2 C1 C2 30mA L U N V CONTACTS RATING Max switching voltage 230VAC 220 VDC Max switching power 62 5VA 30W OUT DIAGRAM B POWER SUPPLY AND MOTOR 1x48 230Vac Vdc SW3 1x110 230Vac SW1 2 Press to rel...

Страница 32: ...8 SWITCHMATIC 1 3 116 77 5 50 75 G1 4 F NPT 1 4 F 116 77 5 50 75 G1 4 f NPT 1 4 f SWITCHMATIC 1 2 SWITCHMATIC 2 3 in out SWITCHMATIC 2 V14_06 2022 DIAGRAM D DIMENSIONS...

Отзывы: