3
P-BUT-
TON
TOUCH
ACTION
click!
From state ON
: unit OFF.
From state OFF
: the pump starts and
keeps operating until reaching Pstop.
From any configuration MENU
: the
parameter value is accepted.
HOLD
DOWN
From state ON
: unit OFF.
From state OFF
: the pump starts and
keeps operating until the push-button
is released.
click!
Pstart is displayed on the screen for 3
seconds.
3”
Pstart adjustment mode.
click!
Pstop is displayed on the screen for 3
seconds.
3”
Pstop adjustment mode.
click!
Is displayed on the screen instantaneous
current consumption.
If it is already displayed then we switch
to instantaneous pressure view.
3”
Rated current adjustment.
8. STARTUP (diagram C)
Before starting the device please read the previous sections,
especially “Hydraulic Installation” and “Electrical connec-
tion”.
Follow next steps:
1. Only for type SW2 set the pump rated current intensity value.
- Press during 3 seconds.
- The current intensity value is displayed on screen, LED A
lights up and display is flashing.
- By mean of and
is adjusted the rated current reflected
in the characteristics plate of the motor. See Note 1.
- Press for validation.
2. Start the device by pressing .
3. Set the cut-in (start) pressure:
- Press during 3 seconds.
- The start pressure value is displayed on screen, LED START
lights up and display is flashing.
- By mean of and is adjusted the start pressure from 0,5
to 7 bar (+ version=11 bar).
- Press for validation.
4. Set the cut-out (stop) pressure:
- Press during 3 seconds.
- The stop pressure value is displayed on screen, LED STOP
lights up and display is flashing.
- By mean of and is adjusted the stop pressure from 1 to
8 bar (+ version=12 bar).
- Press for validation.
5. The unit is ready to operate but more optional adjustments can
be set through basic and advanced MENUS. See the next chapter.
Remark 1: it is important to introduce exactly the rated
current specified on the nameplate of the pump.
9. BASIC MENU
+
(diagram C)
- Press simultaneously + during 5 seconds.
- By mean of or the values can be changed.
- Press for validation.
- The parameters sequence is:
it
TYPE
SYSTEM REACTION
FACTORY
SETTING
1 BAR P We can select the pressure units
displayed beetween bar and psi.
bar
2 rc0 rc2
Fast-cycling alarm:
- rc0: alarm unabled.
- rc1: activated, when hammering is
detected it is delayed the start
in order to protect the pump.
- rc2: alarm is activated and the
pump is stopped upon detec-
tion.
rc2
2.1 r.01 r.99
Only if fast-cycling alarm has been
activated in the previous step
(rc1&rc2). It can be choosed the
maximum time period between 3
consecutive starts that will be con-
sidered fast cycling (between 1 sec.
and 99 sec.)
3 seconds
3 Sb0 Sb1
Stand-by mode activated (Sb1), for
low power consumption, or unabled
(Sb0).
Sb0