DESCRIPTION

SYSTEM REACTION

TYPE

If the system detects dry running during
more than 10 seconds, it will stop the
pumps and the

will be activated. If

there is installed an external device as a
level sensor, when this one detects lack
of water it will stop inmediately the
pumps.The system will show the
message of lack of water.

ART

The system pumps are protected
against over currents by mean of the
intensity values established in the
installation menu. These over currents
are produced generally by dysfunctions
in the pump or in the electric supply.

After 5 minutes

system will start again the first pump during 30 seconds,

trying to restore the system. In case of persistent dry running, it will try it again
every 30 minutes for 24 hours. If after all these cycles , the system still detects
lack of water, pumps will remain permanently off until the damage will be
repaired.
In the case of having an external level sensor, if this device detects enough level
of water again, it will start up the system automatically.

ART

EW

EW

EW

When detecting the thermal failure, the affected pump will be automatically

excluded.

the operating mode

(Emergency

Working) is activated and the secondary pumps will continue working until the
system will be pressurized. If the secondary pumps has been stopped and there
is a new demand of water supply, the system will try again to restart the
excluded pump. The control system will carry out 4 attempts in this
circumstances. If the system remain locked after the 4th attempt, the main
pump will remain definitively out of order and system will continue working
provisionally in

mode until the damage could be repaired.

: The main pump continue working.The

system will try again to restart the excluded pump when the demand of
consumption require it. The control system will carry out 4 attempts in this
circumstances. If the system remain locked after the 4th attempt, the pump will
remain definitively out of order and system will continue working provisionally in

mode until the damage could be repaired.

If the main pump has been excluded

If a secondary pump is excluded

:

A1
DRY RUNNING

A2
OVER-INTENSITY P2_4

SUMMARY OF ALARMS

This device has an electronic safety
system against short circuits for the
main pump as well as a 20 A fuse.
Secondary pumps are protected with 10
A fuses (see diagram 3)

If the system is working in

mode

without the main pump, it analyzes
periodically the state of the expansion
tanks of the hydraulic installation.

EW

The operating mode

(Emergency Working)

is activated allowing the

system to continue running.

EW

If there is not enough accumulation, the system will stop.

A3
DISCONNECTED PUMP

A4
ACCUMULATION

The presure transducer damages are
showed in the LCD screen.

The system has a cooling device to keep
the INVERTER of the main pump in
optimum operating conditions.

If an

excessive temperature is reached, the
own system leaves it out of service and
as consequence the main pump.

The system has an electronic system for
protection against short circuits as well
as a fuse of 20 A.

The device operation is interrupted.

The operating mode

(Emergency Working) is activated, allowing to the

system continue working with secondary pumps. In the model with three
pumps, the auxiliary ones are alternated in each new operating sequence.

EW

The pump remains stopped for 10". Then it starts again - 4 attempts. If the

problem is not solved, the  pump will remain definitively out of order.

A5
TRANSDUCER

A6
EXCESSIVE TEMP.

A7
SHORTCIRCUIT

If led-light failure is flashing intermittently the device is verifying the failure. In case of being permanently bright the failure is definitive.
In case of simultaneous alarms, quit the automatic mode and go to manual mode, pressing the pushbutton "AUTOMATIC". Using key p will be displayed the
succesive alarms. If you want to exit from the menu press ENTER. To restore manually a device turned off by an alarm quit the automatic mode by pressing the
pushbutton "AUTOMATIC ON/OFF" and then press ENTER.
This device has a volt-free contact with 1 A of maximum intensity for the transmission of diferent types of signal (optical, acoustics, etc). See connections diagram
Fig. 3.

The system has an electronic safety
system against overvoltages.

This device has an electronic safety
system against too low supply voltages.

The temperature sensor is damaged, it
can´t measure the instantaneous
temperature or the measuring is
wrong.
EEPROM memory damaged

Blank screen.

In case of overcurrent the system remains stopped during some seconds. Then
the operation is restored.

In case of undervoltage the system remains stopped until an adequate value of
voltage is reached. In this case the system is automatically restored.

The device operation is interrupted.

The device operation is interrupted.

BLANK SCREEN

A8
OVERVOLTAGE

A9
UNDERVOLTAGE

A10
Tu SENSOR

A11
EEPROM

Содержание SPEEDMATIC SET 2010

Страница 1: ...SPEEDMATIC SET 2010 2110 21110 3010 3110 31110 INSTALLATION AND OPERATING INSTRUCTIONS Warning symbols contained in this service manual Risk by electric shock Risk for people and or objects EN RUS...

Страница 2: ...1 Pump 3 only mod 3010 31110 3 3010 31110 Pump 2 2 Nivel m nimo opcional Alimentaci n general NO NC C MAX MIN COVER CONNECTIONS Pump 1 fuse 1 Pump 2 fuses 2 1 2 General fuse 20A 20A Pump 3 fuses 3 Ax...

Страница 3: ...N R S T YELLOW GREEN BLUE 5c POWER SUPPLY N R S T YELLOW GREEN BLUE BROWN SPEEDMATIC SET 2010 3010 PUMP 2 and 3 2 3 5b 5a 3 230 V 1 230 V W U V V U W M 1 1 230 V 6c POWER SUPPLY N R S T YELLOW GREEN B...

Страница 4: ...r 0 98 bar Pw Available minimum pressure in last floor usually 1 5 bar Pc Pressure drop It can be considered with a simplified criteria as 0 033 bar m Prmin Minimum resultant pressure It is the sum of...

Страница 5: ...es or problems of the system Connections for detection of minimum water level in aspiration tank This system is independent of the safety against dry operation Is optional Inside pressure transducer C...

Страница 6: ...a new field of the CONFIGURATION MENU Whenever we want to quit the configuration sequence press MENU 5 8 Led lights LINE green Electric supply ON when it is connected FAILURE red Bright or intermitte...

Страница 7: ...by mean of magnetothermic switch in OFF mode The earth conductor must be longer than the others It will be the first one to to be mounted during the assembly and the last one to to be disconnected dur...

Страница 8: ...se By mean of keys 0 1 we can change it Press ENTER for validation 6 On type 2010 using the START STOP pushbutton corresponding to pump 2 verify its rotation sense In case of reversed sense quit the m...

Страница 9: ...wing the type of view chosen in the previous section Press AUTOMATIC in order to quit manual mode pq pq REGISTER OF FUNCTIONS AND ALARMS Pushing simultaneously MENU during 3 we will get the register o...

Страница 10: ...es see diagram 3 If the system is working in mode without the main pump it analyzes periodically the state of the expansion tanks of the hydraulic installation EW The operating mode Emergency Working...

Страница 11: ...ould be verified and they should be replaced if it is necessary Fig 3 The wound of the motor and the pump consumption should be also verified Once the problem have been solved the operation will be re...

Страница 12: ...0 3010 3110 31110 2 3 SPEEDMATIC SET 7 2 2010 2110 21110 3 3010 3110 31110 3010 3110 31110 LCD Hm 10 1 0 98 Pw 1 5 Pc 0 033 Prmin 5 15 0 Hm 15 1 5 Pw 1 5 Pc 15 x 0 033 0 5 Prmin 1 5 1 5 0 5 3 5 1 Prmi...

Страница 13: ...8 G 1 ISO 228 ART Automatic Reset Test EW AUTOMATIC 9 LCD STAR STOP AUTOMATIC LED APP AIS 5 0...

Страница 14: ...FAILURE ON P1 1 ON P2 2 ON P3 3 3010 3110 311110 2010 3010 3x400 Vca 320 440 50 60 10 A 3x230 2110 3110 1x230 Vca 160 250 50 60 10 A 3x230 21110 31110 1x230 Vca 160 250 50 60 9 A 1x230 2 5 A 3x400 Y...

Страница 15: ...SPEEDMATIC SET 21110 1 5 SPEEDMATIC SET 31110 1 5 1 2010 3010 380 400 2110 3110 21110 31110 220 240 1 R S T N OFF SPEEDMATIC SET FAILURE 15 SPEEDMATIC SET MANUAL LED AUTOMATIC AUTOMATIC AUTOMATIC ON O...

Страница 16: ...RO POMPA 2 VERIFICARE SENSO GIRO POMPA 3 SENSORE LIVELLO NO P LAVORO P META 0 0 bar 0 0 bar MENU PROGRAMMAZIONE PRESSIONE META 2 2 bar ENTER ENTER MENU 0 MENU 3 1 LANGUAGE ENGLISH LANGUE FRAN AISE LIN...

Страница 17: ...01 A18 2003 UNE EN 60730 2 6 1997 A1 1998 A2 1999 CORR A1 2001 CORR A2 01 UNE EN 61000 6 2 2002 UNE EN 61000 6 4 2002 UNE EN 61000 3 2 2001 UNE EN 61000 3 3 1997 CORR 1999 A1 2002 Dichiaramo sotto la...

Страница 18: ...10 ART 5 ART 30 30 24 EW 4 4 EW 4 4 EW A1 A2 P1_3 20A 10A 3 EW EW A3 A4 20A EW 10 4 4 A5 A6 A7 LED AUTOMATIC p ENTER ENTER EEPROM A8 A9 A10 A11 EEPROM...

Страница 19: ...START STOP 15 40 C 50 C 230 380 20A 3 A1 A2 P1_4 A3 A4 A5 A6 A7 A8 A9 A10 A11 EEPROM...

Страница 20: ...130600D 01_2012...

Отзывы: