To start configuration sequence push
MENU
during 3”.
By mean of the
START/STOP
push-button is v
(0/1) it can be changed. Press ENTER for validation.
erified the rotation sense. By mean of keys
p
q
By mean of keys
p
q
we can increase the lower limit of the speed of rotation of the pump´s
motor.
If the installation does not have level probe press
ENTER
to validate NO.
If the installation has a level probe, use keys
p
q
to change NO by YES.
Being inside configuration menu we are having access to the phase of programmation.
This will be the system operating pressure. Use keys
p
q
to modify the initial value (2 bar).
WARNING ! The input pressure must be al least 1 bar lower than the maximum pressure of
the pumps.
NOTE
: In case of group assembly, all the system operates at the pressure set in the MASTER device,
so that the configuration of set pressure in the slave device is superfluous.
By mean of keys
p
q
input the nominal current intensity value in A of the pump, enabling the
thermal protection. This value is located over the characteristics plate of the motor. Press
ENTER
for validation. (Is recommended to enter a current vaule 15% higher than the nominal value).
There are 2 view modes to choose:
n
NORMAL
: it is visualized “P LINE” (real pressure of the installation) and “INPUT P” (configured
pressure).
n
SERVICE
: it is visualized “Hz” (working frequency of the inverter), “SET” (configured pressure),
“P.LINE” (real pressure of the installation) y “FL” (flow sensor state).
TIMER STOP
default value is 5”. This will be the employed time by the system in stopping once
ceased the consumption in all the installation. Using keys
p
q
we can modify the initial value.
The default value is 0,6 bar. This value of pressure is substracted to the system setpoint, resulting
the final pressure to which the system will set in motion the pump when the hydraulic network has
a demand. Use keys
p
q
to modify the initial value. It is recommended to maintain this value
between 0,3 and 0,6 bar. Example:
n
Input pressure: 2 bar.
n
Differential start: 0,3 bar
n
Final start pressure: 2 - 0
,6 = 1,4 bar.
By mean of keys
p
q
we can choose the languages: “LANGUAGE ENGLISH”, “LANGUE
FRANÇAISE”, “LINGUA ITALIANA” and “IDIOMA ESPAÑOL”.
The SPEEDMATIC is configured by default as “SLAVE”.
n
In case of individual assembly just confirm “SLAVE” by pushing
.
n
In case of group assembly (M-S), we will do the same for the slave device. For the
“MASTER” device we will change “SLAVE” by “MASTER” pushing
q
.
n
In case of assembly of more than 2 devices, we will change “SLAVE” by “SWITCHER”
pushing
q
twice - see instructions of our station
SPEEDCENTER.
ENTER
It allows to set the communication channel whe the sation
SPEEDCENTER
is connected. Push
ENTER
.
After pressing
ENTER
pushbutton, the system will remain configured showing the type of view
chosen in the previous section 11. Press
AUTOMATIC
in order to quit manual mode.
In case of group assembly press
AUTOMATIC
only in the device configured as MASTER.
4
2
3
0
1
5
6
7
8
9
10
11
12
13
14
LINE SET P
00,0 bar 00,0 bar
PROGRAMMING MENU
SET PRESSURE
02,0 bar
TIMER STOP
5 s
DIF. START
0,3 bar
MAX. INT. PUMP
OFF
ROTATION SENSE
MIN. SPEED
LEVEL PROBE
0 0 Hz
15 Hz
NO
LANGUAGE
ENGLISH
SET UP MENU
P. LINE SET P
00,0 bar 00,0 bar
VIEW MODE
SERIAL CONTROL
DIRECTION
NORMAL
SLAVE
CH: 1
Being inside configuration menu we are having access to the phase of installation.
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
3”
3”
In case of group assembly, after pressing AUTOMATIC in the MASTER device, the AUTOMATIC LED LIGHT of the SLAVE device
will start to flash intermittently, indicating that communication between both devices is ready. If this does not happen verify the
connection (fig 7).
ON
OFF
CONFIGURATION
Using
p
q
we can change the values and push
ENTER
for validation. After every
ENTER
are sequenced the successive messages that make
up the configuration process.Whenever we want to quit the configuration sequence press
MENU
being saved the modified parameters untill this
point.
-11-