CO2 Meter RAD-0002 Скачать руководство пользователя страница 3

Sym

 

bol 

Mean

 

ing 

Descr

 

iption 

O2 Concentration 

ppm (Parts Per 

Million) 

ambient O2 concentration 

Alarm 

alarm icon 

DIAG

 

Diagnose 

Test communications between the SEU and RDU 

AL1 

(Depletion) 

O2 

The relay 1 will be triggered when O2 concentration is lower than 

AL1. The Red 1 LED and Fault LEDs will flash, buzzer will sound 

and relay1 will be activated. If strobe is connected, the strobe will 

flash and this status will be latched. 

AL2 

(Depletion) 

2nd O2 Alarm level 

The relay 2 will be triggered when O2 concentration lower than 

the second alarm level The Red1, Red 2 LEDs and Fault LEDs 

will flash, and buzzer will sound. Relay1, relay2 will be activated. 

If strobe is connected, the strobe will flash and this status will be 

latched. 

AL3 

(Depletion) 

3rd O2 Alarm level 

When O2 concentration lower than the 3rd alarm level The Red1, 

Red 2, Red3, and Fault LEDs will flash, and buzzer will sound. 

Relay1, relay2, relay3 will be activated. If strobe is connected, the 

strobe will flash and this status will be latched. 

AL1 

(Enrichment) 

 

O2 

The relay 1 will be triggered when O2 concentration higher than 

AL1. The Red 1 LED and Fault LEDs will flash, buzzer will sound 

and relay1 will be activated. If strobe is connected, the strobe will 

flash and this status will be latched. 

AL2 

(Enrichment) 

2nd O2 Alarm level 

The relay 2 will be triggered when O2 concentration higher than 

the second alarm level. The Red1, Red 2 LEDs and Fault LEDs 

will flash, buzzer will sound and relay1, relay2 will be activated. If 

strobe is connected, the strobe will flash and this status will be 

latched. 

AL3 

(Enrichment) 

3rd O2 Alarm level 

When O2 concentration higher than the 3rd alarm level. The 

Red1, Red 2, Red3, and Fault LEDs will flash, buzzer will sound 

and relay1 ,relay2 , relay3 will be activated. If strobe is connected, 

the strobe will flash and this status will be latched. 

CALI 

Calibration 

To calibrate the O2 sensor when the accuracy deviates from the 

actual O2 concentration. 

RCFS 

Recover Factory 

Setting 

To recover factory default settings and cancel any customized 

settings. 

Hi 

High 

The O2 concentration is above 25% 

3. LCD Display Symbols

Fan Icon

Running if buzzer beeps

Содержание RAD-0002

Страница 1: ...he oxygen concentration falls below 19 5 per OSHA requirements The RAD 0002 O2 Monitor is cost effective and has many features including Separate SEU Main Sensor Unit and RDU Remote Display Unit allow...

Страница 2: ...O Battery Backup Input P DC Power Supply Q RDU Cable RJ45 R Relay 3 for AL3 S Relay 2 for AL2 T Relay 1 for AL1 U Strobe Cable RJ45 V Mount Panel Holder RDU Remote Display Unit A Power Green LED B Al...

Страница 3: ...and this status will be latched AL1 Enrichment O2 The relay 1 will be triggered when O2 concentration higher than AL1 The Red 1 LED and Fault LEDs will flash buzzer will sound and relay1 will be acti...

Страница 4: ...indicator LED Relay 1 Relay2 Relay3 Audible Strobe till RESET on SEU regardless the rise of O2 level There are O2 AL1 Enrichment O2 AL2 Enrichment O2 AL3 Enrichment three alarm levels for O2 Enrichmen...

Страница 5: ...the terminal block 24VAC must be converted to 24VDC for the monitor to operate 8 Installation 1 First choose a suitable location near a wall outlet to install the main sensor unit or SEU You should u...

Страница 6: ...y connected the yellow fault LED on the SEU will blink after startup If the cable is inserted into the wrong port on the back of the RDU after about one minute Er7 will flash on the RDU display Secure...

Страница 7: ...unction On Off The alarm ships with the LATCH function off this allows the device to work its way out of alarm status on its own The function can be switched to on meaning alarms will continue until t...

Страница 8: ...und on the SEU and RDU simultaneously 1 4 Using the DIAG function 1 Press Mode until the DIAG icon flashes 2 Press Enter this five LED s will blink on the SEU and the buzzer will sound 3 This five LED...

Страница 9: ...gh 16 0 16 5 17 0 17 5 4 Press Enter again save or press Mode not save quit the setting Setting the O2 Third Alarm parameter of depletion 1 Press Mode until the AL3 O2 icon flashes and depl displays 2...

Страница 10: ...l begin flashing 8 After approximately 3 minutes the LCD will display either PASS or FAIL 9 If the LCD reads FAIL repeat the steps again If it displays PASS press Enter The display should now show 21...

Страница 11: ...the buzzer of SEU and RDU sound simultaneously it indicates that SEU and RDU work normally 12 Safety Notes Warning Your safety is very important to us To ensure to use the product correctly and safet...

Страница 12: ...ion is below first alarm level Response Time 20 30 minutes Operating Conditions Operating Temperature 32 F to 122 F 0 C to 50 C Humidity Range 0 95 RH non condensing Storage Conditions Storage Tempera...

Страница 13: ...r5 flash Fault LED blink Power on again or press reset button if the Er5 always appear please contact with the local dealer 3 Er7 Internal Data Transmission Error Er7 flash Fault LED blink Er7 flash F...