Chapter 5 - MODBUS-RTU Communication
75
Items
Specifications
Control procedure
Asynchronous communication system
Communication system
Half duplex system
Character system
ASCII (8 bit)
Stop bit length
Modbus-RTU: 1 bit, CMC BUS: 2 bit
Sum check
2 byte
Parity check
None
5.3 Installation
5.3.1 Connecting the communication line
-
First connect the 485 GND of MODBUS-RTU communication line to the inverter’s (CM) terminals of
the control terminals.
-
Then connect the MODBUS-RTU communication line to the inverter’s (S+), (S-) terminals of the
control terminals.
-
Check the connection and turn ON the inverter.
-
If the communication line is connected correctly set the communication related parameters as the
following:
-
Operate with DriveView if DriveView is operating, if not operate with the Keypad.
DRV-03 [Drive mode] : 3(RS485)
DRV-04 [Freq. mode] : 5(RS485)
I/O-46 [Inv. Number] :1~31 (If more than 1 inverters are connected, be sure to use different numbers
for each inverter)
I/O-47 [Baud-rate] : 9,600 bps (Factory default)
I/O-48 [Lost Mode] : 0 - No action (Factory default)
I/O-49 [Time-Out] : 10 – 1.0sec (Factory default)
I/O-50 [Comm.Prot] : 7 - Modbus-RTU, 0 – CMC BUS
5.3.2 System
configuration
- The number of drives to be connected is up to 31 drives.
- The specification of length of communication line is max. 1200m. To ensure stable communication, limit
the length below 700m.
- Use shielded wire for all control signal wiring.
Thinkpad
RS232/485
Converter
INV.#
1
Comm.
Terminal
INV.#2
Comm.
Terminal
INV.#n
Comm.
Terminal
JP1 switch on the
right upper side of
control terminal
block should be
shorted using jumper
to connect a
terminating resistor
at the end inverter
connected.