Size
21
31
41
51
71
81
91
101
121
131
141
Maximum water side pressure
kPa
550
550
550
550
550
550
550
550
550
550
550
Safety valve calibration
kPa
600
600
600
600
600
600
600
600
600
600
600
Min. installation water contents
l
17
20
25
33
40
50
53
57
63
68
74
Power supply
Standard power supply
230/1/50
230/1/50
230/1/50 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission
delegated Regulation (EU) No 811/2013 (rated heat output ≤ 70 kW at specified reference conditions) and the
Commission delegated Regulation (EU) No 813/2013 (rated heat output ≤ 400 kW at specified reference conditions)
1. Entering/leaving water temperature user side 30/35°C, Entering external exchanger air temperature 7 °C (R.H.
= 85%)
2. The overall power absorbed is calculated by adding the power absorbed by the comp the power
absorbed by the fan - the percentage value of the fan to overcome external pressure drop + the power absorbed
by the pump - the percentage value of the pump to overcome pressure drop o the power absorbed by
the auxiliary electrical circuit
3. COP (EN 14511:2013) heating performance coefficient. Ratio between delivered heating capacity and power
input in compliance with EN 14511:2013
4. COP Tax credit calculated according to EN14511:2008
5. Entering/leaving water temperature user side 40/45°C, Entering external exchanger air temperature 7 °C (R.H.
= 85%)
6. Entering/leaving water temperature user side 45/55°C, Entering external exchanger air temperature 7°C (R.H.
= 85%)
7. Entering/leaving water temperature user side 23/18°C, external exchanger entering air 35°C
8. EER (EN 14511:2013) cooling performance coefficient. Ratio between delivered cooling capacity and power input
in compliance with EN 14511:2013
9. EER Tax credit calculated according to EN14511:2008
10. ESEER calculated by Clivet for radiant systems with water produced at 18°C by taking into account the load
conditions and source water temperature as defined by EUROVENT for water at 7°C
11. User side entering/leaving water temperature 12/7 °C, external exchanger entering air 35°C
12. ESEER calculated by EUROVENT, for systems featuring terminal units with water produced at 7°C
13. PHE = plate exchanger
14. RAD = radial fan
15. Seasonal Space Heating Energy Efficiency Class according to Commission delegated Regulation (EU) No
811/2013. W = Water outlet temperature (°C)
The heads are intended as available at the unit connections
The pressure drops of the steel mesh strainer, supplied with the unit, have been already taken into consideration
Admissible water flow rates
Min. (Qmin) and max. (Qmax) water flow-rates admissibles for the correct unit operation.
Size
21
31
41
51
71
81
91
101
121
131
141
Minimum flow
[l/s]
0,15
0,18
0,18
0,23
0,34
0,32
0,32
0,32
0,45
0,45
0,45
Maximum flow-rate
[l/s]
0,90
0,90
0,90
1,10
1,50
1,70
1,70
1,70
1,90
1,90
1,90
Содержание WSN-XIN 101
Страница 4: ...4 WSN XIN 21 141 M0V940M13 06...
Страница 13: ...M0V940M13 06 WSN XIN 21 141 13 4 5 GMX Supply grille Accessory Fix the grille with the screws...
Страница 48: ...48 WSN XIN 21 141 M0V940M13 06 Fan replacement...
Страница 60: ...60 WSN XIN 21 141 M0V940M13 06 10 7 Cabinet for Elfo Pool...
Страница 61: ...M0V940M13 06 WSN XIN 21 141 61 1 Cooling operation with parameter r5 0 2 Heating operation with parameter r5 1...