14 WSN-XIN
21-141
M0V940M13-06
5 Water
connections
5.1 Water
quality
The water quality must be checked by qualified personnel.
Water with inadequate characteristics can cause:
•
pressure drop increase
•
reduces energy efficiency
•
increased corrosion potential
Acceptable water quality values:
SO
4
2-
HCO
3
-
/SO
4
2-
Total Hardness
Cl
-
PO
4
3-
< 100
> 1
4,5 ÷8,5
< 50
< 2,0
NH3
< 0,5
PH
7,5 ÷9,0
ppm
dH
ppm
ppm
ppm
Fe
3
+
Mn
++
CO
2
H
2
S
Temperature
< 0,5
< 0,05
< 50
< 50
< 65
Oxygen content
< 0,1
Free Chlorine
< 0,5
ppm
ppm
ppb
°C
ppm
ppm
ppm
Provide a water treatment system if values fall outside the limits.
5.2 Risk of freezing
If the unit or the relative water connections are subject to temperatures close to 0°C:
•
mix water with glycol, or
•
safeguard the pipes with heating cables placed under the insulation, or
•
empty the system in cases of long non-use
5.3 Anti-freeze
solution
The use of an anti-freeze solution results in an increase in pressure drop.
Make sure that the glycol type utilized is inhibited (not corrosive) and compatible with the water circuit components.
Do not use different glicol mixture (i.e. ethylene with propylene).
5.4 Water
flow-rate
The project water-flow must be:
•
inside the exchanger operating limits (see the TECHNICAL INFORMATION section)
•
guarantee, also with variable system conditions (for example in systems where some circuits are bypassed in particular situations).
5.5 Flow
Switch
The flow switch must be present to ensure shutdown of the unit if water is not circulating.
It has to be installed in a duct rectilinear part, not in proximity of curves that cause turbulences.
A
!
A
A > 5 Ø
Ø
A.
minimum
distance
Содержание WSN-XIN 101
Страница 4: ...4 WSN XIN 21 141 M0V940M13 06...
Страница 13: ...M0V940M13 06 WSN XIN 21 141 13 4 5 GMX Supply grille Accessory Fix the grille with the screws...
Страница 48: ...48 WSN XIN 21 141 M0V940M13 06 Fan replacement...
Страница 60: ...60 WSN XIN 21 141 M0V940M13 06 10 7 Cabinet for Elfo Pool...
Страница 61: ...M0V940M13 06 WSN XIN 21 141 61 1 Cooling operation with parameter r5 0 2 Heating operation with parameter r5 1...