4
$&2867,&&21),*85$7,21(;75(0(/</2:12,6((1
*(1(5$/7(&+1,&$/'$7$
W
X
Standard supply
V
400/3/50
Cooling capacity (1)
kW 447.7 508.2 594.1 671.5 720.6 787.5 867.5 1008
1085
1137
1244
1312
Compressor input
kW 169.8 197.7 218.5 243.1 284.6
323
358.8 364.2
430
464.6 507.8 544.4
Total input power
kW 185.2 215.6 235.7 263.9
309
349.6 383.8 397.2 469.8 504.6 550.7 592.7
Compressor type
01
!-3'
#T0+%U#(V
Compressors No.
Nr
2
2
2
2
2
2
2
3
3
3
3
3
Nominal power (C1)
HP 100
130
130
150
180
180
220
150
180
180
180
220
Nominal power (C2)
HP 130
130
150
150
180
220
220
150
180
180
220
220
Nominal power (C3)
HP
-
-
-
-
-
-
-
150
180
220
220
220
Capacity control steps
STD
Nr
6
6
6
6
6
6
6
9
9
9
9
9
Refrigerant circuits
Nr
2
2
2
2
2
2
2
3
3
3
3
3
B
68U=6>?
;
7@>6A
Type
Tube bundle
Number
Nr
1
1
1
1
1
1
1
1
1
1
1
1
Water flow
l/s 21.4
24.3
28.4
32.1
34.4
37.6
41.4
48.2
51.8
54.3
59.4
62.7
Pressure drops
kPa 31
27
34
39
44
58
41
54
74
58
80
90
Water volume
l
114
222
206
206
184
222
252
252
295
462
423
423
:;
8<=6>?
;
7@>6A
Front surface
m
2
29.4
29.4
35
35
35
35
35
54
54
54
54
54
.)"/#%!&'(0#+("1
23!54/&!0
Tipo ventilatori
axial
Numero ventilatori
Nr
10
12
10
12
14
14
14
18
20
22
20
22
Portata aria standard
l/s
35300 39900 44400 50615 56530 56530 56530 72800 78700 82900 78700 82900
66789
6
Water fittings
“
6
8
8
8
8
8
8
8
8
8
8
8
(1) data referred to the following conditions:
internal exchanger water = 12/7°C
room temperature = 35°C
23(5$7,21/,0,76&22/,1*
6,]H
:3;
8<=6>?
;
7@>6A
1 °C 42.5
42.5
43
42.5
42
41
41
42
42
41
41
41
Max. air inlet
temperature
2 °C
45
45.5
46
46.5
46
45
45
46
45.5
46.5
45.5
45
3 °C
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
4 °C
-2
-4
-6
-6
-5
-5
-5
-7
-6
-6
-5
-5
5 °C
10
10
8
8
8
8
8
9
9
9
8
10
Min. air inlet
temperature
6 °C
18
17
17
16
17
17
16
16
16
17
18
18
B
68<=6>?
;
7@>6A
Max water inlet
temperature
7 °C
21
21
21
21
21
21
21
21
21
21
21
21
8 °C
6
6
6
6
6
6
6
6
6
6
6
6
Min water outlet
temperature
9 °C
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
Note: In any case, the unit should never be exposed to or operated, transported and/or stored at temperatures below -10°C.
C
>=63E6AGF8D@8DE?E?3>EY76J
8D
6Z
[M>68>\>O67\P>EPD?
Q]8\8D@\S363
8
. Any wind condition can let air pass through the
condenser coil thus worsening the operating limits of the unit (see limits with air speed at 0,5 m/s & 1 m/s). In order to avoid such
situation, windbreak barriers are necessary. The minimum ambient temperature is given for units equipped with low ambient
control or with ECObreeze fans.For standard unit without these options, this value is of about 18°C with still air and unit operating
at full load.
(1) unit at full load
(2) capacity-controlled unit (automatic capacity control)
(3) unit at full load external exchanger air 35°C
(4) unit at partial load (automatic capacity control) air to external exchanger 35°C
(5) unit at partial load (automatic capacity control) air to external exchanger = 0.5m/sec
(6) unit at partial load (automatic capacity control) air to external exchanger 35°C
(7) external exchanger air intake 35°C
(8) Standard Version external exchanger air intake 35°C
(9) Low temperature version external exchanger air intake 35°C
Fluid with ethylene glycol of 40%