30
Hour
tE31
tE59
tE87
Minutes
tE32
tE60
tE88
Mode 0= on
1= standby
tE33 tE61 tE89
Cooling
temperature
tE34 tE62 tE90
Heating
temperature
tE35 tE63 tE91
DHW
temperature
tE36 tE64 tE92
Hour
tE24
tE52
tE80
Minutes
tE25
tE53
tE81
Mode 0= on
1= standby
tE26 tE54 tE82
Cooling
temperature
tE27 tE55 tE83
Heating
temperature
tE28 tE56 tE84
DHW
temperature
tE29 tE57 tE85
Hour
tE17
tE45
tE73
Minutes
tE18
tE50
tE74
Mode 0= on
1= standby
tE19 tE47 tE75
Cooling
temperature
tE20 tE48 tE76
Heating
temperature
tE21 tE49 tE77
DHW
temperature
tE22 tE50 tE78
7 - CONTROL
Main menu Parameter modification
Parameters
tE
tE00
It is possible to set 3 different schedulings.
To each schedulino is possible to associate 4 events.
To each day of the week is possible to associate a scheduling.
In the example the schedulings have been assigned:
scheduling 1
Monday, Tuesday, Wednesday
scheduling 2
Thursday, Friday
scheduling 3
Saturday, Sunday
Day
Scheduling
1
Scheduling
2
Scheduling
3
Monday
tE01 = 1
-
-
Tuesday
tE02 = 1
-
-
Wednesday
tE03 = 1
-
-
Thursday
-
tE04 = 2
-
Friday
-
tE05 = 2
-
Saturday
-
-
tE06 = 3
Sunday
-
-
tE07 = 3
Description
Event 1
Event 2
Event 3
Hour
tE10 = 07 tE17 = 12
tE24 = 16
Minutes
tE11 = 00 tE18 = 00
tE25 = 30
Mode 0= on
1= standby
tE12 = 0
tE19 = 0
tE26 = 0
*
Cooling
temperature
tE13 = -
tE20 = -
tE27 = -
*
Heating
temperature
tE14 = 20 tE21 = 22
tE28 = 22
DHW
temperature
tE15 = 45 tE22 = 45
tE29 = 55
Scheduling 1
Event 4
tE31 = 22
tE32 = 00
tE33 = 0
tE34 = -
tE35 = 18
tE36 = 45
In the following example the
scheduling 1
schedules:
at 07:00
changes the heating set-point
at 12:00
changes the heating set-point
at 16:30
changes the DHW set-point
at 22:00
changes the heating set-point and DHW
Sched. 1
(par.)
Sched.2
(par.)
Sched.3
(par.)
Hour
tE10
tE38
tE66
Minutes
tE11
tE39
tE67
Mode 0= on
1= standby
tE12
tE40
tE68
Cooling
temperature
tE13
tE41
tE69
Heating
temperature
tE14
tE42
tE70
DHW
temperature
tE15
tE43
tE71
Ev
en
t 2
Ev
en
t 3
Ev
en
t 4
Ev
en
t 1
*
If the unit is in Cooling is used the cooling temperature.
*
If the unit is in Heating is used the heating temperature.
7.3 SCHEDULING MANAGEMENT
To enable the hour scheduling :
Par
tE00 hour scheduling
0 = disabled , 1 = enabled
Par CL43 = -2 (see pag 15)
Содержание WSAN-XIN 21