20
5 - ELECTRICAL CONNECTIONS
HEATING
Example :
dS02 = 20°C
dS04 = - 7°C
dS06 = -5°C
setpoint = 35°C
Compensated setpoint = 28°C
t ext °C
15°C
-5°C
35°C
28°C
setpoint
dS02 > 0
dS04
t ext °C
dS06
Setpoint
dynamic
differential
Heat
description
dS02
Differential proportional zone in Heat on external air
dS04
Max water set dynamic differential in Heat
dS06
Set point dynamic differential of external air
5.12 WATER SET POINT COMPENSATION WITH
AMBIENT TEMPERATURE
Only with ambient keyboard option .
Function and parameters are the same of 5.11 paragraph.
On the ambient keyboard set parameter Cr 30 = 10
It is possible enable ambient compensation OR external
compensation, not ambient AND external compensation.
With outside mild temperatures the thermal requirements are
reduced.
The internal comfort can also be obtained with a lower set-
point.