M06K40A18-00
CKN-XHE2i 7.1-14.2
4
9.6 Indoor air coil
Contact with the exchanger fins can cause cuts: wear protective gloves to perform the above described operations.
The finned surfaces of the cooling coils and, in particular, the condense collection bowls constitute places where microorganisms and moulds
greatly flourish.
It is very important to foresee periodical cleaning with suitable detergents and, eventually, disinfect with sanitising products.
9.7 Electric fans
Check:
•
the fans and the relative protection gridsare well fixed
•
the fan bearings (evident by noise and anomalous vibrations)
•
the terminal protection covers are closed and the cable holders are properly positioned
9.8 Condensation collection basin
Dirt or scale can give rise to clogging.
Also, microorganisms and mould can flourish in the bowl.
It is very important to foresee periodical cleaning with suitable detergents and, eventually, disinfect with sanitising products.
Once cleaning is completed, pour water inside the bowl to check the regular outflow.
9.9 crankcase heather
Check:
•
closure
•
Operation
9.10 G4 Folded air filters
It is very important for the air treatment coil to offer maximum thermal exchange: the unit must always work with clean and installed filters.
Cleaning and replacement of filters are very important from an hygienic-sanitary point of view.
Operation with clogged filters leads to a reduction in the air flow rate with malfunctionings and block, up to possible breaks in the unit.
The frequency with which the filters must be checked depends on the quality of the air, the unit operation hours, the dustiness and crowding
of rooms.
Frequency can indicatively vary from WEEKLY to MONTHLY.
It is advised to start with frequent checks, subsequently adjusting frequency to degree of detected dirt.
1. Remove the closing panels
2. Delicately remove the filter avoiding dirtying the area below
3. Wash the filtering jacket in warm water with common detergent
4. Accurately rinse in running water avoiding spilling in the room
5. Dry the filter
6. Insert it back in its seat
7. Remount the closing panels
Old filters, washing wastewater and residues must be disposed of according to the current standards.
Содержание CKN-XHE2i 10.1
Страница 7: ...M06K40A18 00 CKN XHE2i 7 1 14 2 7...
Страница 16: ...16 CKN XHE2i 7 1 14 2 M06K40A18 00 6 5 Connections performer by customer...
Страница 44: ...M06K40A18 00 CKN XHE2i 7 1 14 2 44 Fans...
Страница 45: ...4 CKN XHE2i 7 1 14 2 M06K40A18 00 VALVES Only value 14 2...
Страница 51: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 Flue stack assembly...
Страница 53: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 10 6 Hot water coil...
Страница 65: ......