22
CKN-XHE2i 7.1-14.2
M06K40A18-00
7.8 Voltages
Check that the air and water temperatures are within in the operating limits.
Start-up the unit.
With unit operating in stable conditions, check:
•
Voltage
•
Total absorption of the unit
•
Absorption of the single electric loads
7.9 Remote controls
Check that the remote controls (ON-OFF etc) are connected and, if necessary, enabled with the respective parameters as indicated in the
“electrical connections” section.
Check that probes and optional components are connected and enabled with the respective parameters (“electrical connections” section and
following pages).
7.10 Air flow management
Standard mode
The delivery air flow stays constant as the thermal load varies.
The ventilation remains active even when the setpoint is fulfilled.
Constant air flow rate
Option
The delivery air flow rate stays constant during variations in the thermal load and head losses of the unit and system.
The ventilation remains active even when the setpoint is fulfilled.
Variable airflow
Option
The air flow supply varies depending on the heat load, up to a minimum value compatible with the distribution system and the chosen air
diffusion.
The ventilation remains active even when the setpoint is fulfilled.
7.11 Air flow setting
Standard mode
The real unit flow is according to the aeraulic system features.
Before checking, make sure that the system has been completed in all its parts (shunts, dampers, grilles, diffusers etc.).
Check the doors and windows of the serviced room are closed.
The unit must be calibrated while full recirculation has been running for at least 30 minutes.
The unit is in full recirculation during the first 60 minutes of operation.
Set the fan’s percentage of operation:
FanSpeedOutMand
Содержание CKN-XHE2i 10.1
Страница 7: ...M06K40A18 00 CKN XHE2i 7 1 14 2 7...
Страница 16: ...16 CKN XHE2i 7 1 14 2 M06K40A18 00 6 5 Connections performer by customer...
Страница 44: ...M06K40A18 00 CKN XHE2i 7 1 14 2 44 Fans...
Страница 45: ...4 CKN XHE2i 7 1 14 2 M06K40A18 00 VALVES Only value 14 2...
Страница 51: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 Flue stack assembly...
Страница 53: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 10 6 Hot water coil...
Страница 65: ......