CLIVET CKN-XHE2i 10.1 Скачать руководство пользователя страница 18

18 

CKN-XHE2i 7.1-14.2 

M06K40A18-00

Take a slotted-head screwdriver and insert it into the recess on the lower part of the controller, then turn the screwdriver to lower the back 

cover. (Pay attention to the rotation direction, or the back cover may get damaged!)
Use three GB950-86 M4X20 screws to install the back cover directly onto the wall.
Use two GB823-88 M4X25 screws to install the back cover in the electrical junction box 86 and use one GB950-86 M4X20 screw to install it 

directly onto the wall.
Adjust the length of the two plastic plugs to the standard distance from the threaded bar of the wall-mounted switch box. When inserting the 

plastic plugs into the wall, make sure that the lie flush with the wall.
Use Phillips-head screws to fasten the back cover of the controller to the wall using the plastic plug. Make sure that the back cover of the 

controller lies at the same level after installation and mount the controller back onto the rear cover.
Install the back cover correctly and securely fasten both the front and back covers, otherwise the front cover could fall.

Содержание CKN-XHE2i 10.1

Страница 1: ...M06K40A18 00 08 05 18 CKN XHE2i 7 1 14 2 Installation and operating manual High efficiency Roof Top air cooled heat pump...

Страница 2: ...he installation and maintenance cost for the life cycle of the system The purpose of this manual is to provide you with information that is useful from reception of the equipment through installation...

Страница 3: ...eneral description 2 Reception 3 Positioning 4 Water connections 5 Aeraulic connections 6 Electrical connections 7 Start up 8 Control 9 Maintenance 10 Accessories 11 Decommissioning 12 Residual risks...

Страница 4: ...by inexperienced personnel they may cause damages to things and injuries people 1 4 Intended use Use the unit only civil air conditioning keep to the limits foreseen in the technical schedule and in t...

Страница 5: ...vate the unit Contact a service centre authorized by the manufacturer The installer must train the user particularly on Start up shutdown Set points change Standby mode Maintenance What to do what not...

Страница 6: ...dvice of receipt to supplier and the carrier Any disputes must be made within 8 days from the date of the delivery Complaints after this period are invalid 2 1 Storage Observe external packaging instr...

Страница 7: ...M06K40A18 00 CKN XHE2i 7 1 14 2 7...

Страница 8: ...M06K40A18 00 2 3 Packaging removing Be careful not to damage the unit Keep packing material out of children s reach it may be dangerous Recycle and dispose of the packaging material in conformity wit...

Страница 9: ...for the air intake exhaust max distance allowed by the electrical connections install the unit raised from the ground verify unit weight and bearing point capacity verify that all bearing points are a...

Страница 10: ...ulation of snow and ice in front of the exhaust air outlet 3 3 Saftey valve gas side The installer is responsible for evaluating the opportunity of installing drain tubes in conformity with the local...

Страница 11: ...s 2 FISSARE LE FINITURE DX E SX Esternamente e internamente sugli appositi fori con le viti in dotazione 2 FIX RIGHT and LEFT PARTS With screws supplied on the appropriate holes internal and external...

Страница 12: ...XTERNAL AIR EA With screws supplied on the appropriate holes La piega deve andare verso l esterno della cuffia The fold must be installed on the external side of the air hood 3 6 Electronic filter For...

Страница 13: ...werage drainage network DO NOT use white water or drainage networks to avoid the aspiration of odours in the case of evaporation of water contained in the siphon Check at the end of the work the regul...

Страница 14: ...them with deflectors in particular with high air speed or bends with reduced radius 5 1 Treated air channelling The internal surface of the channel must be smooth enable its washing and must not cont...

Страница 15: ...t full load power input at max admissible condition Electrical wiringdiagram Nr 6 2 Connections 1 Refer to the unit electrical diagram the number of the diagram is shown on the serial number label 2 V...

Страница 16: ...16 CKN XHE2i 7 1 14 2 M06K40A18 00 6 5 Connections performer by customer...

Страница 17: ...hey could trigger a fire Do not place the controller near lamps in order to prevent potential interferences with the controller signal Do not install the unit in a place subject to excessive amounts o...

Страница 18: ...one GB950 86 M4X20 screw to install it directly onto the wall Adjust the length of the two plastic plugs to the standard distance from the threaded bar of the wall mounted switch box When inserting th...

Страница 19: ...o water penetrates inside the controller use mastic and other contraptions to seal the cable connectors during installation Adjust the front cover then fasten it avoid blocking the cables during insta...

Страница 20: ...OFF power supply 1 safety access 2 functional spaces 3 air flow correct return and supply no bypass no stratification 4 structure integrity 5 fans run freely 6 unit on vibration isolators 7 air filte...

Страница 21: ...nd at worst cases can cause damages to the exchangers and the other parts Weight of glycol 10 20 30 40 Freezing temperature C 3 9 8 9 15 6 23 4 Safety temperature C 1 4 10 19 7 6 Electric Circuit Veri...

Страница 22: ...fulfilled Constant air flow rate Option The delivery air flow rate stays constant during variations in the thermal load and head losses of the unit and system The ventilation remains active even when...

Страница 23: ...ECO mode the renewal air is not managed The ECO mode can be activated Manually P04 Enable EcoMode 1 Automatically by means supervision system Example in cooling mode 7 13 Operating mode The set point...

Страница 24: ...24 CKN XHE2i 7 1 14 2 M06K40A18 00 Fixed set point Manual mode Fixed set point Automatic mode Variable set point Manual mode Automatic set point Automatic mode...

Страница 25: ...entifying the operating objective conditions is useful to control the unit over time With unit at steady state i e in stable and close to work conditions identify the following data total voltages and...

Страница 26: ...y the set value The parameter can be rapidly modified by pressing it extendedly OK To confirm an operation ON OFF To set the ON OFF function BACK To return to the previous level Press to exit the curr...

Страница 27: ...ative humidity Unit status indicator on when the unit is running Compressor indicator on when the compressor is running Auxiliary electric heater indicator on when the auxiliary electric heater or H2O...

Страница 28: ...ect Press to adjust the temperature if the sensor is enabled Press OK to confirm If no operations are made for more than 10 sec the system automatically memorises the settings and returns to the home...

Страница 29: ...to return to the home page If ENMode 0 or 2 in the ASSISTANCE menu the mode operation is disabled If ENMode 3 in the ASSISTANCE menu the mode and eco mode operations are disabled Operating mode Choose...

Страница 30: ...ord Press to enter the value of the password The password is 123 and cannot be modified If the password is incorrect the display will appear as follows After entering the correct password the display...

Страница 31: ...cted days After the selection press OK to view the next page Press to choose timer T1 T5 Press ON OFF to enable disable the selected timer Press ON OFF to enable disable ECO function Press to select e...

Страница 32: ...to confirm or BACK to cancel the operation and return to the previous page When AUTO TEMP SETTING ON manual adjustment of the temperature is disabled Shown to the side is the page that appears when t...

Страница 33: ...displayed as If EnDiffMand 0 is set on the controller QSetMand is disabled QSetMand and QAir are displayed as If EnProbe 0 is set on the controller SetCO2 is disabled SetCO2 and VOC are displayed as...

Страница 34: ...tection H4 10 interventions of the protection module in 120 minutes H9 Outdoor fan fault HE EXV disconnection alarm F8 Expulsion fan F9 TF probe fault C0 Heating elements high temperature alarm C1 Hum...

Страница 35: ...SETTINGS Select INTERFACE SETTING To shift the cursor press select ON or OFF To adjust the value press To select the language press SERVICE INFORMATION Select SERVICE INFORMATION To shift the cursor p...

Страница 36: ...8 Data bits Parity bit None Parity Stop bit 1 stop bit 4 Function code Unit address is setted by the encoder called NET ADRESS The unit address is corresponding with Encoder setting 1 eg if it is set...

Страница 37: ...setpoint 0 100 3 Constant airflow setpoint set m3 h 4 Enable Auto Temperature 0 OFF 1 ON 5 Enable ECO Mode 0 OFF 1 ON 6 Air quality setpoint set ppm 7 void 8 void 9 void 10 void Status Register number...

Страница 38: ...9 T2 25 C 70 C 220 T3 25 C 70 C 221 T4 25 C 70 C 222 TP1 25 C 70 C 223 TP2 25 C 70 C 224 TF1 0 C 140 C 225 TF2 0 C 140 C 226 T2B 25 C 7 0 C 227 Tw 25 C 70 C 228 Pfin 0 Pa 2000 Pa 229 Pfout 0 Pa 2000 P...

Страница 39: ...6E 6F 70 71 72 73 74 75 76 77 78 Fault code L0 L1 L2 L3 L4 L5 L6 L7 L8 L9 LA LB LC LD LE LF LH LL LP LU LOW BYTE Hex 79 7A 7B 7C 7D 7E 7F 80 81 82 83 84 85 86 87 88 89 8A 8B 8C Fault code J0 J1 J2 J3...

Страница 40: ...limits etc critical use service necessary intervention frequency months 1 6 12 1 presence corrosion X 2 panel fixing X 3 fan fixing X 4 coil cleaning X 5 bowl cleaning sanitisation X 6 outflow test X...

Страница 41: ...er to what is indicated in the start up section Schedule technical assistance in advance to avoid hitches and to guarantee that the system can be used when required 9 5 Outdoor air coil Contact with t...

Страница 42: ...owl to check the regular outflow 9 9 crankcase heather Check closure Operation 9 10 G4 Folded air filters It is very important for the air treatment coil to offer maximum thermal exchange the unit mus...

Страница 43: ...leaning state fastening presence of corrosion 9 14 Immersed electrode humidifier Accessory For details see 10 3 Immersed electrode humidifier p 49 9 15 access to the components Probes and transducers...

Страница 44: ...M06K40A18 00 CKN XHE2i 7 1 14 2 44 Fans...

Страница 45: ...4 CKN XHE2i 7 1 14 2 M06K40A18 00 VALVES Only value 14 2...

Страница 46: ...rgent and water at 1 20 3 Immerse the filter in this solution 4 Ensure the solution covers the entire filter 5 A slight chemical reaction is noticed within 2 3 minutes with the development of foam Wai...

Страница 47: ...dirty they must be replaced 1 Open the access panel 2 Delicately remove the filter avoiding dirtying the area below 3 Insert the new filters with the pockets vertically 4 Close the panel 5 Dispose of...

Страница 48: ...rate of the installed humidifier DRAINAGE WATER It can reach a temperature of 100 C It contains the same substances of the supply water but in higher concentration As it is not toxic it can be dispose...

Страница 49: ...e of humidifier by means of the unit isolator remove the vapour pipe from the cylinder disconnect the electric connections of the electrodes and remove the pins from the high level electrodes loosen t...

Страница 50: ...al standards in force install on the gas connection tap large section filter and anti vibration joint check the supply pressure is correct and stable in particular where more uses are inserted on the...

Страница 51: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 Flue stack assembly...

Страница 52: ...l standards in force install on the gas connection tap large section filter and anti vibration joint check the supply pressure is correct and stable in particular where more uses are inserted on the s...

Страница 53: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 10 6 Hot water coil...

Страница 54: ...covered by the legislation in question are marked with the symbol on the side With the aim of protecting the environment all of our units are produced in compliance with Directive EC on waste electric...

Страница 55: ...Periodically check that all of the panels are correctly closed and fixed If there is a fire the temperature of the refrigerant could reach values that in crease the pressure to beyond the safety valv...

Страница 56: ...otor 6 EC Brushless EC Brushless EC Brushless Installed unit power 8 kW 0 9 0 9 1 0 External Section Fans Type of fans 9 AX AX AX Number of fans Nr 1 1 1 Fan diameter mm 750 750 780 Fan RPM 6 EC Brush...

Страница 57: ...he unit operating at full load To verify the operation field of the operating units with percentages of external air always calculate the Tm mixing temperature at the internal heat exchanger input TM...

Страница 58: ...ing in free field conditions External static pressure 50 Pa standard UNI EN ISO 9614 2 Measures are according to UNI EN ISO 9614 2 regulations with respect to the EUROVENT 8 1 certication which provid...

Страница 59: ...ate drain 6 H2O heating coil output 3 4 7 H2O heating coil input 3 4 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 H2O heating coil optional or heating elements optional 12...

Страница 60: ...ndensate drain 6 H2O heating coil outpu 1 7 H2O heating coil input 1 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 H2O heating coil optional or heating elements optional 12...

Страница 61: ...sate drain 6 H2O heating coil outpu 1 1 4 7 H2O heating coil input 1 1 4 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 H2O heating coil optional or heating elements optional...

Страница 62: ...t 4 Humidifier connections 5 Condensate drain 6 Gas connection 7 Condensate drain only for condensation gas heating module 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 Resi...

Страница 63: ...ut 4 Humidifier connections 5 Condensate drain 6 Gas connection 7 Condensate drain only for condensation gas heating module 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 Res...

Страница 64: ...ut 4 Humidifier connections 5 Condensate drain 6 Gas connection 7 Condensate drain only for condensation gas heating module 8 Re heating coil optional 9 Internal exchanger 10 External exchanger 11 Res...

Страница 65: ......