M23740N6-03 01/10/07
page
23
LIST OF THE PARAM ETERS ACCESSIBLE BY THE THERM OSTAT
Par Description
range
UM Def.
P01 BandaLavoro
: Working band
0
÷
15.0
°C 2.0
P02
MaxH2Ocool:
Water max. temperature for cooling operating
0
÷
30.0
°C 20.0
P03
MinH2OHeat
:
Water min. temperature for heating operating
0
÷
40.0
°C 30.0
P05
TimeOnPeriodical
Defines the duration of the ON phase of the periodical
0
÷
999
min 2
P06
TimeOffPeriodical
Defines the duration of the OFF phase of the periodical
0
÷
999
min 5
P10
OffsetEco
0
÷
4.0
°C 3.0
P11 SetUrHeat
: Heat UR set point
30
÷
70
% 50
P12 BandUrHeat
: Intervention band of the heat humidifier
0
÷
10
% 5
P21
FanOffCool
:
Fan status at “cooling” thermoregulator, satisfied.
0: stop, 1: continuous , 2: periodical
0…2 num
2
P22
FanOffHeat
:
Fan status at “heating” thermoregulator, satisfied.
0: stop, 1: continuous , 2: periodical
0…2 num
0
P31
ModoAuto
:
It enables the automatic saison change
0: Manual, 1: Auto
0…1 flag
0
P41
BT1 probe calibration
-9.9 +10.0
°C
0.0
P42
BT2 probe calibration
-9.9 +10.0
°C
0.0
P43
Thermostat temp. probe calibration
-9.9 +10.0
°C
0.0
P44
Thermostat UR probe calibration
-9.9 +10.0
%UR
0.0
S01 TESToperativa
°C
S02 TH2Ooperativa
°C
S03 TARIAoperativa
°C
S04 URoperativa
Hr%
S05 Actual
mode
bitmap
S06 CurrentSetpoint
°C
S07
Current humidity Set
Hr%
S08 Errors
bitmap
S09 Active
humidifcation
flag
S10
Active dehumidification
flag
S11 FanStatus
: 0: off, 1: on
0…1 flag
S12
Actual fan:
0-7 if motor 0-10 V
0-3 if 3 speed motor
0-1 if single-speed motor
0…7 num