background image

 

CLT- & CLX-1DIM8

 

Functional Summary 

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

The Crestron

 1-Feed, 8-Dimmer Terminal Block and 

Module (CLT-1DIM8 and CLX-1DIM8, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-1DIM8 prior to installation of the 
CLX-1DIM8, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate the circuit feed (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
dimming control of eight incandescent, magnetic low 
voltage, neon, cold cathode, or dimmable 2-wire 
fluorescent lighting loads. The maximum load is 16 amps 
for any controlled circuit, limited to 16 amps total per 
module. The unit requires 120VAC 60 Hz, 1 phase input 
voltage. An oversize heat sink dissipates heat efficiently. 
There are LEDs on the module to indicate communication 
to a Cresnet

 network, input power to the module, and 

output power to the load. 

Terminal Block & Module Locations (Single-wide Enclosure) 

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

MODULE

 

 

Industry Compliance 

This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc.  

     

(E103692)

 

Terminal Block & Module Locations (Double-wide Enclosure) 

TERMINAL BLOCK

(RIGHT)

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

MODULE

 

Installation 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
32

°

F to 104

°

F (0

°

C to 40

°

C). The relative humidity 

must be 0% to 90% (non-condensing).  

Crestron Electronics, Inc.

 

Installation Guide – DOC. 5985B

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2002067)

 

Tel: 888.CRESTRON

 

05.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  
 

Содержание CLT-1DIM8

Страница 1: ...NAL BLOCK GROUNDING TERMINAL BLOCK MODULE Industry Compliance This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc E103692 Terminal Block Module Locations Double wide Enclosure TERMINAL BLOCK RIGHT GROUNDING TERMINAL BLOCKS TERMINAL BLOCK LEFT MODULE Installation Terminal block and module must be mounted into a Crestron Automation Enclosure by a licen...

Страница 2: ...l neutrals together Do not remove any bypass jumpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on next page NOTE Use copper conductors only rated 75 C 2 With the circuit breaker turned off connect the circuit feed HOT and NEUTRAL and controlled circuit LOAD wires to the terminal...

Страница 3: ...the terminal to which it should be connected Wires are pre stripped to inch Tighten to 9 in lbs Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the module...

Страница 4: ...arges following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years fr...

Отзывы: