7 - Options:
Electric heating
Heating can be provided by a battery of electrical
resistances.
This battery is integrated into the ventilation module.
An air conditioner is subjected to constant variations in
temperature. This inexorably induces deposits of humidity in the
connection boxes.
In order to prevent this phenomena the connections have to be
offset. For this purpose, each resistance is provided with a 3-metre
power cord.
Reminder: it is imperative to connect the frame of the air
conditioner to the electrical installation's ground.
Cleaning ramp
An automatic cleaning ramp can be mounted in the air
conditioner, even later.
Installation is done from the inside of the ventilation module.
Humidification
The humiliation nozzle is an ultrasound atomizer. These atomizers spray the water
as micro-droplets, similar to fog.
Installation and the adjustments require special attention:
- A stream directed towards a smooth wall would thrust the fog and form drops of water
again.
The effects of the spraying and fogging would then be cancelled.
- The stream produced has to be a fog, not a simple spray. Simple droplets that are
sprayed, but not fogged, are not absorbed by the air.
Installation
The humiliation nozzle is fastened, under the cold battery, to the pan support
crosspiece.
The stream must not be directed towards the battery or the wall of the condensate pan.
It has to be axed towards the opposite corner of the pan.