ECO series ModBus register map

Parameter file 
settings (4x)

Unit/Value

Description

35201

Temperature setpoint 
min limit

0,1 °C

E.g. 200 = 20,0°C.  

NOTE ! Must be dividable by 5 (0,5°C)

35202

Temperature setpoint 
max limit

0,1 °C

E.g. 200 = 20,0°C.  

NOTE ! Must be dividable by 5 (0,5°C)

35203

Temperature setpoint 
normal

0,1 °C

NOTE! Use 4x4 instead

35204

Temperature setpoint 
away

0,1 °C

E.g. 200 = 20,0°C.  

NOTE ! Must be dividable by 5 (0,5°C)

35205

Not used

35206

Week timer master  
off/on

0 = Off, 1 = On

This is same as 4x2000. Does not matter which one you use

35225

Thermostat adaptivity

1 = Off, 1 = On

35226

Temp calibration

0,1 °C

E.g. 10 = +1,0°C

59001

Active week program 
setpoint

0,1 °C

Read only

Input  
registers (3x)

Unit/Value

Description

5

HW revision

6

SW version major

7

SW version minor

8

Room temperature

0,1 °C

9

Not used

10

Not used

11

Application state

12

Application status

13

Not used

14

Temperature setpoint

0,1 °C

15

Last user activity  
(Touch display)

sec

16

Not used

17

Start unit

18

Heating load

%

Содержание ECO-W

Страница 1: ...Ensure that children cannot get their hands on the device 3 Detach the grille 2 from the body Remove the two fastening screws 3 and pull the grille off the body 1 4 Insert the bottom section duct connector into the inlet air duct and attach the body to the wall with screws 4 2 pcs max Ø 5 mm 5 Connect the supply cable MMJ through a double pole switch and the control unit s data cable to the connec...

Страница 2: ...rmostat controls one terminal device there is no need to change the position of the DIP switches One thermostat controls 2 4 terminal devices Position the DIP switches as shown in the figure The air heater is controlled with a 230 V supply voltage without the ECO T controller as shown in Figure 3 4 move the DIP switch No 8 to the ON position NOTE Electrical connections may only be made by a profes...

Страница 3: ...N DIP1 8 Modbus ID L N N L X3 X2 X1 230VAC CONTROL Modbus TERMINATION OFF ON OFF ON DIP1 8 Modbus ID L N N L X3 X2 X1 D D V T B A CONTROL BUS T OFF ON Bus termination by jumper OFF ON Bus termination by jumper CONTROL Modbus ID ID 1 4 1 2 3 4 ECO T D D V T D D V T N L Control BUS B A 230 VAC Room T ECO air heater D D V T N L ECO air heater One ECO T control unit can control 1 4 ECO air heaters Ven...

Страница 4: ...r The ECO connection in which the heating of several rooms has been linked through the bus ON D D V T B A CONTROL BUS BUS Term T OFF D D V T B A CONTROL BUS BUS Term T ECO air heater ECO air heater ECO air heater BUS Modbus ID 1 9 BUS Master ON D D V T B A CONTROL BUS BUS Term T Modbus settings Modbus ID Stop bits Baudrate Master 38400 1 Modbus settings Modbus ID Stop bits Baudrate 1 38400 1 Modbu...

Страница 5: ...via a BMS Building Management System device D D V T N L Control BUS 230 VAC Room 1 Slave ECO T D D V T B A T ECO air heater D D V T N L ECO air heater One ECO T control unit can control 1 4 ECO air heaters One ECO T control unit can control 1 4 ECO air heaters ECO T D D V T D D V T N L Control BUS B A 230 VAC Room 2 T ECO air heater BMS Slave Master Figure 4 3 ...

Страница 6: ...The temperature can be adjusted in the main view with the plus and minus symbols 8 More detailed instructions on the system functions are provided in a separate manual 2 Controller installation 1 Run the ECO T controller unit s data cable from the ECO air heater to the junction box as shown in Figure 2 1 2 Detach the touch screen 4 from the locking piece 3 3 Detach the locking piece from the botto...

Страница 7: ...econ 7 Installation manual ECO W NOTE Electrical connections may only be made by a professional electrician Always disconnect the device from the supply voltage before maintenance OFF 1 3 5 2 4 2x 2x 2x 2x 230 VAC Data ...

Страница 8: ...tenance manual ECO W NOTE Maintenance may only be performed by a professional ventilation installer Warning The device carries a voltage of 230 V Disconnect from the supply voltage before maintenance OFF 1 3 5 2 4 6 2x 3x 4x 1 0 ...

Страница 9: ...m 1 Comfort end time Minutes after midnight 0 0 00 NOTE Must be dividable by 15 2005 Week program 1 Comfort temperature 0 1 C E g 200 20 0 C NOTE Must be dividable by 5 0 5 C 2006 Week program 1 Economy temperature 0 1 C E g 200 20 0 C NOTE Must be dividable by 5 0 5 C 2007 Week program2 off on bit 0 Monday off on bit 1 Tuesday off on bit 2 Wednesday off on bit 3 Thursday off on bit 4 Friday off o...

Страница 10: ...fort end time Minutes after midnight 0 0 00 NOTE Must be dividable by 15 2023 Week program 4 Comfort temperature 0 1 C E g 200 20 0 C NOTE Must be dividable by 5 0 5 C 2024 Week program 4 Economy temperature 0 1 C E g 200 20 0 C NOTE Must be dividable by 5 0 5 C 2025 Week program5 off on bit 0 Monday off on bit 1 Tuesday off on bit 2 Wednesday off on bit 3 Thursday off on bit 4 Friday off on bit 5...

Страница 11: ... 20 0 C NOTE Must be dividable by 5 0 5 C 35205 Not used 35206 Week timer master off on 0 Off 1 On This is same as 4x2000 Does not matter which one you use 35225 Thermostat adaptivity 1 Off 1 On 35226 Temp calibration 0 1 C E g 10 1 0 C 59001 Active week program setpoint 0 1 C Read only Input registers 3x Unit Value Description 5 HW revision 6 SW version major 7 SW version minor 8 Room temperature...

Страница 12: ...unt 104 alive count 105 alive count 106 alive count 107 alive count 108 alive count 109 alive count 110 alive count 111 Number of UI slave devices 112 alive count 113 alive count 114 alive count 115 alive count 116 alive count 117 alive count 118 alive count 119 alive count 120 alive count 50020 UI serial number low byte 50021 UI serial number high byte ...

Отзывы: