English 05/09
ACCURATE AX - AW - AD - AT - AF
61
TROUBLESHOOTING
A
I
U
Troubleshooting is simplified by the information provided by the
microprocessor controller: if an alarm is signalled, refer to the
control panel instruction manual.
If required, contact the nearest service centre, indicating the
probable causes of the fault.
Check for voltage; close the main switch.
The electrical panel is not powered
Check that the cutout IM in the auxiliary cir-
cuits is armed.
Check the fuse on the main board.
The auxiliary circuits are not powered
Check for DC power.
The control panel does not start the
air-conditioner.
FAULT
CAUSE
SOLUTION
THE AIR-CONDITIO-
NER DOESN'T START
See the controller manual.
The parameter settings on the microprocessor
controller are not correct.
See “LOW OR NO AIR FLOW”.
The air flow-rate is too low or null.
Check the electrical connections and the
configuration of the controller.
The probe isn't working.
Check the thermal load in the room being
air-conditioned.
Thermal load higher than expected.
See “THE COMPRESSOR/COMPRESSORS
DON'T START”.
The compressor/compressors don't start,
despite being activated by the controller.
ROOM TEMPERATURE
TOO HIGH
See the controller manual.
The parameter settings on the
microprocessor controller are not correct.
Check that the heater thermal cutout is armed.
Check the power supply to the electric heaters.
If the heater safety thermostat is activated,
resolve the causes and reset the alarm.
The power of the heaters is not sufficient or
the heaters aren't working.
Check the flow-rate and the temperature of
the water hot.
Check the operation of the control valve
and the servomotor.
The hot water coil isn't working correctly.
Check the operation of the hot gas three-way
valve;
Check the operation of the compressor used
for post-heating: in this case, see “THE
COMPRESSOR/COMPRESSORS DON'T
START”.
The hot gas post-heating system isn't working
during the dehumidification plus post-heating
phase
ROOM TEMPERATURE
TOO LOW