POSITIONING THE AIR-CONDITIONER
A
I
U
The air-conditioner can rest directly on the floor, perfectly level,
with a maximum difference in height of 5 mm between the ends
of the base: incorrect levelling may cause the condensate to leak
from the collection pan.
WARNING:
the air-conditioner must be installed indoors
and in non-aggressive environments. Apply an elastic gasket
around the perimeter of the base to prevent the transmis-
sion of noise and vibrations.
SUPPORT FRAME (optional accessory)
A support frame is recommended:
- to allow the air-conditioner to be installed before assembling
the raised floor;
- to totally dampen any mechanical vibrations;
- to assist the laying of pipes and cables.
The support frame is available as an accessory and is adjustable in
height, indicated in the figure by the distance X, between 200 and
600 mm.
To prevent the transmission of noise and vibrations, an elastic gas-
ket, at least 5 mm thick, should be inserted between the panels of
the raised floor and the frame, which must also be insulated from
the metallic structure of the floor.
NOTE:
the frame must be fitted by the installer following the
instructions shown inside the packaging.
L1
P1
X
X = 200 ÷ 600
mm
L1(mm)
600
1000
980
1530
2080
2630
P1(mm)
485
485
770
770
770
770
07
10
15
18
20
26
29
39
30
40
50
55
60
70
80
90
Raised floor
Elastic gasket
Elastic gasket
ACCURATE
unit
OPERATING SPACE
A
I
U
D
L
E
Access is from the front only for all models.
This feature ensures easy access to all the main components in
the unit for installation and periodical maintenance.
Thanks to this feature, the units can be installed next to one
another, or alternatively fitted in racks.
To ensure easy maintenance, a space of at least 600 mm must be
left in front of the air-conditioner, as shown in the figure.
Make sure that the air intake and outlet are never
blocked, even partially.
D mm
>600