ACCURATE AX - AW - AD - AT - AF
37
REFRIGERANT CONNECTIONS (AX)
A
I
U
DIAMETERS OF THE CONNECTIONS INSIDE THE UNIT
The diameter of connecting pipes between the conditioner and condensing unit must be respected, otherwise the guarantee becomes
invalid. Always use large radius curve (bending radius at least equal to pipe diameter)
NOTE:
The diameter of the refrigerant lines between the air-conditioner and the remote condenser (OD) must be chosen according to
the length of the lines, and therefore this will not always coincide with the inside diameter of the joint to be welded supplied by the manu-
facturer. Special care must be paid to the insulation of the hot gas pipes under the raised floor.
RECOMMENDED OUTSIDE DIAMETERS OF THE LINES (for equivalent lengths up to 30m)
Model
07
10
18
20
26
29
39
30
40
50
55
80
90
15
60
70
Ø Liquid Line (mm)
12
12
16
12
16
18
Ø Gas Outlet Line (mm)
12
18
22
18
22
22
Models
7
10
15
18
29
39
30
40
60
70
80
90
20
26
50
55
GAS
PIPELINE TYPE
DIAMETER PIPE mm
R407C
Liquid line
12
16
18
2x16
2x16
2x18
Discharge line
18
22
22
2x22
2x22
2x22
2x22
R410A
Liquid line
10
14
16
2x14
2x16
2x16
Discharge line
16
18
22
2x18
2x22
2x22
2x22
Equivalents lenght in meters of: curve, shut-off and non-return valve
Nominal diameter
(mm)
90°
45°
180°
90°
12
0,50
0,25
0,75
2,10
1,90
14
0,53
0,26
0,80
2,20
2,00
16
0,55
0,27
0,85
2,40
2,10
18
0,60
0,30
0,95
2,70
2,40
22
0,70
0,35
1,10
3,20
2,80
28
0,80
0,45
1,30
4,00
3,30