![CLIMAVENETA Accurate AD Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/climaveneta/accurate-ad/accurate-ad_installation-manual-user-maintenance_2624837054.webp)
54
English 05/09
ACCURATE AX - AW - AD - AT - AF
1
2
3
4
5
SQX82...
3-position positioning signal
• Voltage on Y1: actuator stem extends, valve opens
• Voltage on Y2: actuator stem retracts, valve closes
• No voltage on Y1 and Y2: actuator stem remains in the respec-
tive position
Description
This actuator with 3point or 0÷10V signal is adapt for 2 or 3 way valve with 20mm stroke
Calibration SQX62
The minimum stroke of the valve is 15 mm. The LED does not indicate a calibration error when the stroke is < 15 mm
The stem extends to the maximum position with the maximum positioning signal DC 10 V.
A flashing red LED indicates a calibration error.
SQX62...
Y, R signals: DC 0...10 V
The SQX62 is either controlled via terminals Y and/or R.The
recorded positioning signals control the synchronous motor
by means of microprocessor electronics.
• Signal Y, R increasing: actuator stem extends, valve opens
• Signal Y, R decreasing: actuator stem retracts, valve closes
• Signal Y, R constant: actuator stem remains in the respective
position
SQX82:
SQX62:
1
Terminal strip
2 Button S3 (calibration)
3 LED, red / green (operating status indication)
4 Terminal
strip
5
DIL switches:
switch S1: change-over flow characteristic «
LOG
» /
«LIN»
*
)
switch S2: change-over signal R «
0-10 V, 4-20 mA
» /
«1000
Ω
»
*
)
(
*
) bold print = factory setting
Calibration
1. Pressing button S3 starts calibration
2. Actuator moves to «0 %» stroke position (valve closed)
green LED flashes
3. Actuator moves to «100 %» stroke position (valve open)
4. Measured values saved in microprocessor
Normal operation
5. Actuator moves to the position as indicated by signals Y or R
green LED is lit permanently