G e o t h e r m a l H e a t i n g a n d C o o l i n g
Trilogy
®
Variable
(VE) Series IOM - 60Hz HFC-410A
C r e a t e d : 4 O c t o b e r, 2 0 1 9
Troubleshooting (Cont.)
Code
Fault
Mode
Possible Cause
Solution
10
ECM Low RPM
ALL
Blower does not operate
Check blower line voltage
ALL
Blower does not operate
Check blower low voltage wiring
ALL
Blower operating
with incorrect airflow
Wrong unit size selected - check unit configuration
ALL
Blower operating with
incorrect airflow
Wrong unit family selected - check unit configuration
ALL
Blower operating
with incorrect airflow
Incorrect motor size
ALL
Blower operating
with incorrect airflow
Incorrect blower selection
11
Low Air Coil Pressure
CL
Low Return Air temp
Bring air temp within design parameters
CL
Plugged air filter
Clean or replace air filter
CL
Bad Suction Pressure
Transducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal at
GND and RED is not between 0.5-4.5 VDC, replace sensor
CL
Insufficient charge
Check for refrigerant leaks
12
Control Fault
ANY
EXM not properly programmed reprogram EXM using Service Tool
ANY
Bad EXM
replace EXM
13
Low Pump Flow
ALL
Flat loop
Flush and repressurize loop.
ALL
Air pocket
Flush and repressurize loop.
ALL
System setup for single and
not parallel pumping.
Change unit loop pump configuration.
ALL
Pump Failure
Check pump.
ALL
Bad Flow Sensor
Check flow sensor.
14
High Discharge temp
ALL
Insufficient charge
Check for refrigerant leaks
HT
Water temp out of range
Bring water temp within design parameters
CL
Air temp out of range
Bring air temp within design parameters
ALL
Faulty EEV
Check EEV operation, superheat will be high as well
ALL
Fouled heat exchanger
Clean appropiate coil
15
Discharge Pressure Sensor
ALL
Bad tranducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal at
GND and RED is not between 0.5-4.5 VDC, replace sensor
ALL
Bad wiring harness
Check harness
ALL
Bad EXM
If supply voltage across BLK and GND doesn’t read 4.5-5.5 VDC replace
EXM
ALL
Bad EXM
If voltage across GND and RED reads between 0.5-4.5 VDC but fault still
exists, replace EXM
16
Suction Pressure Sensor
ALL
Bad tranducer
If supply voltage at BLK and GND wires reads 4.5-5.5 VDC but signal at
GND and BLU is not between 0.5-4.5 VDC, replace sensor
ALL
Bad wiring harness
Check harness
ALL
Bad EXM
If supply voltage across BLK and GND doesn’t read 4.5-5.5 VDC replace
EXM
ALL
Bad EXM
If voltage across GND and BLU reads between 0.5-4.5 VDC but fault still
exists, replace EXM
Содержание Trilogy VE 0930
Страница 2: ...This page was intentionally left blank...
Страница 65: ...65 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes Notes...
Страница 66: ...66 Geothermal Heating and Cooling Trilogy Variable VE Series IOM 60Hz HFC 410A C reate d 4 O ctober 2019 Notes...
Страница 67: ...67 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes...