G e o t h e r m a l H e a t i n g a n d C o o l i n g
Trilogy
®
Variable
(VE) Series IOM - 60Hz HFC-410A
C r e a t e d : 4 O c t o b e r, 2 0 1 9
Troubleshooting
Table 15: Nominal resistance at various temperatures
Temp (ºC)
Temp (ºF)
Resistance
(kOhm)
Temp (ºC) Temp (ºF)
Resistance
(kOhm)
-17.8
0.0
85.34
55
131.0
2.99
-17.5
0.5
84.00
56
132.8
2.88
-16.9
1.5
81.38
57
134.6
2.77
-12
10.4
61.70
58
136.4
2.67
-11
12.2
58.40
59
138.2
2.58
-10
14.0
55.30
60
140.0
2.49
-9
15.8
52.38
61
141.8
2.40
-8
17.6
49.64
62
143.6
2.32
-7
19.4
47.05
63
145.4
2.23
-6
21.2
44.61
64
147.2
2.16
-5
23.0
42.32
65
149.0
2.08
-4
24.8
40.15
66
150.8
2.01
-3
26.6
38.11
67
152.6
1.94
-2
28.4
36.18
68
154.4
1.88
-1
30.2
34.37
69
156.2
1.81
0
32.0
32.65
70
158.0
1.75
1
33.8
31.03
71
159.8
1.69
2
35.6
29.50
72
161.6
1.64
3
37.4
28.05
73
163.4
1.58
4
39.2
26.69
74
165.2
1.53
5
41.0
25.39
75
167.0
1.48
6
42.8
24.17
76
168.8
1.43
7
44.6
23.02
77
170.6
1.39
8
46.4
21.92
78
172.4
1.34
9
48.2
20.88
79
174.2
1.30
10
50.0
19.90
80
176.0
1.26
11
51.8
18.97
81
177.8
1.22
12
53.6
18.09
82
179.6
1.18
13
55.4
17.26
83
181.4
1.14
14
57.2
16.46
84
183.2
1.10
15
59.0
15.71
85
185.0
1.07
16
60.8
15.00
86
186.8
1.04
17
62.6
14.32
87
188.6
1.01
18
64.4
13.68
88
190.4
0.97
19
66.2
13.07
89
192.2
0.94
20
68.0
12.49
90
194.0
0.92
21
69.8
11.94
91
195.8
0.89
22
71.6
11.42
92
197.6
0.86
23
73.4
10.92
93
199.4
0.84
24
75.2
10.45
94
201.2
0.81
25
77.0
10.00
95
203.0
0.79
26
78.8
9.57
96
204.8
0.76
27
80.6
9.16
97
206.6
0.74
28
82.4
8.78
98
208.4
0.72
29
84.2
8.41
99
210.2
0.70
30
86.0
8.06
100
212.0
0.68
31
87.8
7.72
101
213.8
0.66
32
89.6
7.40
102
215.6
0.64
33
91.4
7.10
103
217.4
0.62
34
93.2
6.81
104
219.2
0.60
35
95.0
6.53
105
221.0
0.59
36
96.8
6.27
106
222.8
0.57
37
98.6
6.01
107
224.6
0.55
38
100.4
5.77
108
226.4
0.54
39
102.2
5.54
109
228.2
0.52
40
104.0
5.33
110
230.0
0.51
41
105.8
5.12
111
231.8
0.50
42
107.6
4.92
112
233.6
0.48
43
109.4
4.72
113
235.4
0.47
44
111.2
4.54
114
237.2
0.46
45
113.0
4.37
115
239.0
0.44
46
114.8
4.20
116
240.8
0.43
47
116.6
4.04
117
242.6
0.42
48
118.4
3.89
118
244.4
0.41
49
120.2
3.74
119
246.2
0.40
50
122.0
3.60
120
248.0
0.39
51
123.8
3.47
121
249.8
0.38
52
125.6
3.34
122
251.6
0.37
53
127.4
3.22
123
253.4
0.36
54
129.2
3.10
Sensor Inputs
All sensor inputs are ‘paired wires’ connecting each
component to the board. Therefore, continuity on pressure
switches, for example can be checked at the board
connector. The thermistor resistance should be measured
with the connector removed so that only the impedance of
the thermistor is measured. If desired, this reading can be
compared to the thermistor resistance chart shown in Table
15. An ice bath can be used to check the calibration of the
thermistor.
Содержание Trilogy VE 0930
Страница 2: ...This page was intentionally left blank...
Страница 65: ...65 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes Notes...
Страница 66: ...66 Geothermal Heating and Cooling Trilogy Variable VE Series IOM 60Hz HFC 410A C reate d 4 O ctober 2019 Notes...
Страница 67: ...67 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes...