Unit Operating Conditions
Table 12b: 1860 Pressure and Temperature
1860
Cooling
Entering
Water
Temp
°F
DT
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super
heat
Sub
cooling
Water
Flow GPM
Air Temp
Drop °F
DB
50
20
127-137
208-228
8-12
7-12
10.8-11.8
17-23
15
127-137
186-206
12-16
7-12
10.5-11.5
17-23
10
127-137
163-183
17-21
6-11
10.3-11.3
17-23
70
20
125-135
298-318
8-12
8-13
11.7-12.7
17-23
15
126-136
275-295
8-12
8-13
11.5-12.5
17-23
10
126-136
253-273
8-12
7-12
11.2-12.2
17-23
90
20
120-130
387-407
8-12
10-15
12.6-13.6
17-23
15
122-132
365-385
8-12
10-15
12.4-13.4
17-23
10
123-133
342-362
8-12
9-14
12.2-13.2
17-23
110
20
112-122
477-497
8-12
12-17
13.6-14.6
17-23
15
115-125
454-474
8-12
12-17
13.4-14.4
17-23
10
117-127
432-452
8-12
11-16
13.1-14.1
17-23
1860
Heating
Entering
Water
Temp
°F
DT
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super
heat
Sub
cooling
Water
Flow
GPM
Air Temp
Rise °F
DB
30
11
61-71
340-360
8-12
20-25
5.5-6.5
25-31
8
68-78
337-357
8-12
17-22
8.5-9.5
25-31
5
73-83
333-353
8-12
14-19
11.5-12.5
25-31
50
12
98-108
333-353
8-12
4-9
5.5-6.5
25-31
9
105-115
333-353
8-12
3-8
8.5-9.5
25-31
6
110-120
333-353
8-12
2-7
11.5-12.5
25-31
70
13
135-145
333-353
8-12
1-6
5.5-6.5
25-31
10
141-151
333-353
8-12
1-6
8.5-9.5
25-31
7
148-158
333-353
8-12
1-6
11.5-12.5
25-31
90
14
172-182
333-353
8-12
1-6
5.5-6.5
25-31
11
177-187
333-353
13-17
1-6
8.5-9.5
25-31
8
184-194
333-353
16-20
1-6
11.5-12.5
25-31
Содержание Trilogy VE 0930
Страница 2: ...This page was intentionally left blank...
Страница 65: ...65 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes Notes...
Страница 66: ...66 Geothermal Heating and Cooling Trilogy Variable VE Series IOM 60Hz HFC 410A C reate d 4 O ctober 2019 Notes...
Страница 67: ...67 climatemaster com Trilogy Variable VE Series IOM 60Hz HFC 410A Created 4 October 2 0 1 9 Notes...