Thermostat Installation
- The thermostat should be
located on an interior wall in a larger room, away from
supply duct drafts. DO NOT locate the thermostat in
areas subject to sunlight, drafts or on external walls.
The wire access hole behind the thermostat may in
certain cases need to be sealed to prevent erroneous
temperature measurement. Position the thermostat
back plate against the wall so that it appears level and
so the thermostat wires protrude through the middle
of the back plate. Mark the position of the back plate
mounting holes and drill holes with a 3/16” (5mm) bit.
Install supplied anchors and secure plate to the wall.
Thermostat wire must be 18 AWG wire. Representative
thermostat wiring is shown in Figures 22a-b however,
actual wiring connections should be determined from the
thermostat IOM and or unit wiring diagram. Practically
any heat pump thermostat will work with ClimateMaster
units, provided it has the correct number of heating and
cooling stages.
Electrical - Thermostat Wiring
Field Wiring
Factory Wiring
Figure 22a: Conventional 3 Heat / 2 Cool
Thermostat Connection to DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC32U03
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optiona)
Remote Indoor
Sensor
(Optiona)
24Vac Common
Gnd
R
C
A+
Figure 22b: Communicating Thermostat Connection
to DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC32U03
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optiona)
Remote Indoor
Sensor
(Optiona)
24Vac Common
Gnd
R
C
A+