T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Rooftop (TRE) Series
R e v. : O c t o b e r 7 , 2 0 1 9
15
c l i m a t e m a s t e r. c o m
General Line Voltage Wiring
- Be sure the available
power is the same voltage and phase as that shown on
the unit serial plate. Line and low voltage wiring must
be done in accordance with local codes or the National
Electric Code, whichever is applicable.
TRE Power Connection
- Line voltage connection is
made by connecting the incoming line voltage wires to
the power block. Line voltage conduit should be routed
through curb and unit pipe chase. Terminate conduit at
control/compressor deck.
208 Volt Operation
- All 208-240 Volt units are factory
wired for 208 Volt. The transformers may be switched to
240V operation as illustrated on the wiring diagram by
switching the Red (240V) and the Orange (208V) wires on
the transformer primary side. Unused wire terminal will be
“hot” and must be insulated and secured to prevent an
electric short.
Optional GFI Outlet requires dedicated 115V - 20 AMP
circuit provided by installer
�
WARNING!
�
WARNING!
Disconnect electrical power source to prevent
injury or death from electrical shock.
�
CAUTION!
�
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Figure 2 illustrates a typical trap used with TRE Heat Pumps.
Multiple units within the same zone should be operated
from a common temperature control.
Thermostat Wiring -
All wiring must comply with all
applicable electrical codes including NEC and local
codes. Complete all wiring before units are installed.
Use multi conductor, color-coded, low-voltage cable
for all wiring. Refer to unit wiring diagram for required
thermostat connections.
Table 2: Recommended Thermostat Wire Sizes
* Length = physical length of wire from thermostat to unit.
�
CAUTION!
�
CAUTION!
Maintain zone integrity to assure accurate and
efficient operational control of units or groups of units.
Without adequate zone control, adjacent units may operate in
heating and cooling mode simultaneously.
Electrical Wiring
WIRE SIZE
MAX. WIRE LENGTH*
22 - Gauge
30 feet [9.14m]
20 - Gauge
50 feet [15.24m]
18 - Gauge
75 feet [22.86m]
16 - Gauge
125 feet [38.1m]
14 - Gauge
200 feet [60.96m]
Refer to Table 2 for wire sizes and lengths. Do not allow
the total resistance of all low-voltage wires used to exceed
1 ohm. Resistance in excess of 1 ohm may cause high
voltage drop which may result in control malfunction.
Refer to the thermostat installation and operation manual
to determine recommended heat anticipator settings.
When using a DDC building management system (BMS),
communication grade wire may be required. Verify
required communication and sensor wiring type with the
manufacturer of the BMS system components.