27
c l i m a t e m a s t e r. c o m
P R E L I M I N A RY
Tranquility
®
30 Digital (TE) Series IOM - 60Hz HFC-410A
R e v. : 3 A u g . , 2 0 1 2 B
Electrical - Line Voltage
WARNING!
CAUTION!
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 5a: Tranquility 30
®
(TE) Series Electrical Data
Model
Compressor
HWG
Pump
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
RLA
LRA
Qty
026
11.7
58.3
1
0.5
3.9
16.1
19.0
30
038
15.8
83.0
1
0.5
3.9
19.7
23.5
35
049
21.7
104.0
1
0.5
6.9
28.6
33.9
50
064
27.1
152.9
1
0.5
6.9
34.5
41.2
60
072
29.7
179.2
1
0.5
6.9
37.1
44.5
70
Rated Voltage of 208-230/60/1
Min/Max Voltage of 197/254
HACR circuit breaker in USA only
All fuses Class RK-5
Model
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max/
Fuse
HACR
RLA
LRA
Qty
026
11.7
58.3
1
0.5
1.7
3.9
17.8
20.7
30
038
15.8
83.0
1
0.5
1.7
3.9
21.4
25.2
40
049
21.7
104.0
1
0.5
1.7
6.9
30.3
35.6
50
064
27.1
152.9
1
0.5
1.7
6.9
36.2
42.9
70
072
29.7
179.2
1
0.5
1.7
6.9
38.8
46.2
70
Rated Voltage of 208-230/60/1
Min/Max Voltage of 197/254
HACR circuit breaker in USA only
All fuses Class RK-5
Table 5b: Tranquility 30
®
(TE) Series Electrical Data
with Magna Inernal Flow Controller
Electrical - Line Voltage
All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for fi eld connections that
must be made by the installing (or electrical) contractor.
All fi nal electrical connections must be made with a length of
fl exible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
WARNING!
CAUTION!
WARNING!
Disconnect electrical power source to prevent
injury or death from electrical shock.
CAUTION!
Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Unit Power Supply
(see electrical tables 5a - 5b for minimum
circuit amps and maximum breaker size)
Figure 23: Tranquility Single Phase Line Voltage
Field Wiring
Power Connection
Line voltage connection is made by connecting the incoming
line voltage wires to the “L” side of the contactor as shown in
Figure 23. Consult Tables 5a through 5b for correct fuse size.
Note: always refer to the unit dataplate for unit electrical data.
208 Volt Operation
All residential 208-230 Volt units are factory wired for 230
Volt operation. The transformer may be switched to the 208V
tap as illustrated on the wiring diagram by switching the red
(208V) and the orange (230V) wires at the contactor terminal.