G e o t h e r m a l   H e a t   P u m p   S y s t e m s

P R E L I M I N A RY

Tranquility

®

 30 Digital (TE) Series IOM - 60Hz HFC-410A

R e v. :   3   A u g . ,   2 0 1 2 B

Hot Water Generator

Figure 20: Typical HWG Installation

Figure 21: HWG Double Tank In stal la tion

 

WARNING! 

WARNING!  A 150°F SETPOINT MAY LEAD TO 
SCALDING OR BURNS.  THE 150°F SET POINT MUST 
ONLY BE USED ON SYSTEMS THAT EMPLOY AN 
APPROVED ANTI-SCALD VALVE.

The HWG (Hot Water Generator) or desuperheater option 
provides considerable operating cost savings by utilizing 
heat energy from the compressor discharge line to help 
satisfy domestic hot water requirements. The HWG is active 
throughout the year, providing virtually free hot water when 
the heat pump operates in the cooling mode or hot water at 
the COP of the heat pump during operation in the heating 
mode. Actual HWG water heating capacities are provided in 
the appropriate heat pump performance data.

Heat pumps equipped with the HWG option include a built-
in water to refrigerant heat exchanger that eliminates the 
need to tie into the heat pump refrigerant circuit in the 

fi

 eld. 

The control circuit and pump are also built in for residential 
equipment. Figure 20 shows a typical example of HWG water 
piping connections on a unit with built-in circulating pump. 
This piping layout prevents sludge/debris from the bottom of 
the tank being pulled into the HWG pump.

The temperature set point of the HWG is 

fi

 eld selectable 

to 125°F or 150°F .  The 150°F  set point allows more heat 
storage from the HWG.  For example, consider the amount 
of heat that can be stored by the HWG when using the 125°F 
set point, versus the amount of heat that can be generated 
by the HWG when using the 150°F set point.

In a typical 50 gallon two-element electric water heater 
the lower element should be turned down to 100°F, or the 
lowest setting, to get the most from the HWG.  The tank will 
eventually stratify so that the lower 80% of the tank, or 40 
gallons, becomes 100°F (controlled by the lower element).  
The upper 20% of the tank, or 10 gallons, will be maintained 
at 125°F (controlled by the upper element).

Using a 125°F set point, the HWG can heat the lower 40 
gallons of water from 100°F to 125°F, providing up to 8,330 
btu’s of heat.  Using the 150°F set point, the HWG can heat 
the same 40 gallons of water from 100°F to 150°F and the 
remaining 10 gallons of water from 125°F to 150°F, providing 
a total of up to 18,743 btu’s of heat, or more than twice as 
much heat as when using the 125°F set point.

Electric water heaters are recommended. If a gas, propane, 
or oil water heater is used, a second preheat tank must be 
installed (Figure 21). If the electric water heater has only a 
single center element, the dual tank system is recommended 
to insure a usable entering water temperature for the HWG.

Typically a single tank of at least 50 gallons (189 liters) is used 
to limit installation costs and space. However, a dual tank, as 
shown in Figure 21, is the preferred system, as it provides the 
maximum storage and temperate source water to the HWG.

It is always advisable to use water softening equipment on 
domestic water systems to reduce the scaling potential and 
lengthen equipment life. In extreme water conditions, it may 
be necessary to avoid the use of the HWG option since the 
potential cost of frequent maintenance may offset or exceed 
any savings. Consult Table 3 for scaling potential tests.

Hot Outlet

to home

Insulated water lines - 
5/8” OD, 50 ft maximum (one way)
[16mm OD, 15 meters maximum]

Powered

Water

Heater

Upper

element to

120 - 130°F

[49 - 54°C]

Lower

element to

100 - 110°F

[38 - 43°C]

Shut-off

Valve #3

Shut Off 
Valve #2

Field supplied 3/4’ brass nipple and ‘T’

Cold

Inlet

Shut Off 
Valve #4

Shut Off 
Valve #1

Insulated water lines - 5/8” OD, 50 ft maximum (one way)

[16mm OD, 15 meters maximum]

Upper element to 130°F [54°C]

(or owner preference)

Cold Inlet

Hot Outlet to

house

Powered

Water Heater

Cold Inlet from

Domestic supply

Hot Outlet

Unpowered

Water Heater

Field Supplied 3/4” brass nipple and “T”

Lower element to 120°F [49°C]

Shut-off

Valve #1

Shut-off

Valve #4

Shut-off

Valve #3

Shut Off 
Valve #2

Содержание tranquility 30

Страница 1: ...re Cutout Selection 19 Closed Loop External Central 20 Pumping Applications Open Loop or Ground Water 21 22 Heat Pump Applications Water Quality Standards 23 Hot Water Generator 24 26 Electrical Line...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...th or serious injury CAUTION Indicates a potentially hazardous situation or an unsafe practice which if not avoided could result in minor or moderate injury or product or property damage NOTICE Notifi...

Страница 4: ...dering and shipping information to verify that the correct unit has been shipped 2 Keep the cabinet covered with the original packaging until installation is complete and all plastering painting etc i...

Страница 5: ...nal Service Access Left Rtn right Opposite 2 61cm Service CSP Vertical Unit Location Packaged units are not designed for outdoor installation Locate the unit in an INDOOR area that allows enough space...

Страница 6: ...ping electrical cables and other items that prohibit future removal of components or the unit itself 4 Use a manual portable jack lift to lift and support the weight of the unit during installation an...

Страница 7: ...h sides of the coil A thorough water rinse should follow Figure 6b Typical Ground Water Horizontal Unit Installation with Internal Motorized Modulating Valve Pressure Tank Ball Valves Internal Motoriz...

Страница 8: ...Remove the screws as shown in Figure 7 to free top panel and discharge panel 2 Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful...

Страница 9: ...Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line WHEN...

Страница 10: ...control valves vFlow Configurations 1 Internal Flow Controller For Closed Loop Applications This is the most common configuration for closed loops With this factory installed standard option the unit...

Страница 11: ...ps for new construction before sidewalks patios driveways and other construction has begun During construction accurately mark all ground loop piping on the plot plan as an aid in avoiding potential f...

Страница 12: ...fps 0 6 m s in all piping using a filter in the loop return line of the flush cart to eliminate debris from the loop system See Table 17 for flow rate required to attain 2fps 0 6 m s The steps below...

Страница 13: ...f all air is purged from the system the level will drop only 3 8 in a 10 25 4 cm diameter PVC flush tank about a half gallon 1 9 liters since liquids are incompressible If the level drops more than th...

Страница 14: ...ont of Unit Valve Position the flush cart from the Internal Flow Controller Install Flow Controller caps to ensure that any condensation leakage remains contained within the Flow Controller package If...

Страница 15: ...2 ton units and four loop circuits we can calculate the flushing pressure drop as follows From Table 17 we know that it will take 4 gpm to flush each circuit If there is no provision to isolate the ci...

Страница 16: ...rnal Flow Controllers and External Flushing Valves When the number of units or flushing requirements reaches a point where it is no longer feasible to flush through the internal valves generally syste...

Страница 17: ...ith a central variable speed pump In this case units with closed loop modulating valves are used do not use open loop modulating valves on a closed loop system External flushing valves are required Th...

Страница 18: ...tallation 1 Flush loop until all air has been purged from system and pressurize to check for leaks before adding any antifreeze 2 Run discharge line to a drain and hook up antifreeze drum to suction s...

Страница 19: ...port Repeat if necessary 5 Be careful when handling methanol or any alcohol Always wear eye protection and rubber gloves The fumes are flammable and care should be taken with all flammable liquids Op...

Страница 20: ...ts to closed position if it loses signal but still has 24V power running to it If the motorized modulating valve loses both signal from the DXM2 board AND 24V power it will remain in the same position...

Страница 21: ...s should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system Schrader ports built into unit may be used to measure heat exchanger pressure d...

Страница 22: ...t be chosen as complimentary items For example an expansion tank that is too small can cause premature pump failure due to short cycling Variable speed pumping applications should be considered for th...

Страница 23: ...e Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Part...

Страница 24: ...0 F controlled by the lower element The upper 20 of the tank or 10 gallons will be maintained at 125 F controlled by the upper element Using a 125 F set point the HWG can heat the lower 40 gallons of...

Страница 25: ...ED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER TEMPERATURES DISTRIBUTED TO ALL HOT WATER OUTLETS A...

Страница 26: ...WG and purge air from the HWG piping 2 Open a hot water faucet to vent air from the system until water flows from faucet turn off faucet Open valve 4 3 Depress the hot water tank pressure relief valve...

Страница 27: ...l Line Voltage All field installed wiring including electrical ground must comply with the National Electrical Code as well as all applicable local codes Refer to the unit electrical data for fuse siz...

Страница 28: ...4 5 6 7 8 1 2 3 4 5 6 7 8 Accessory Relays Accessory Terminal The DXM2 controller includes two accessory relays ACC1 and ACC2 Each relay includes a normally open NO and a normally closed NC contact A...

Страница 29: ...n site easier configuration monitoring and diagnosis Figure 26a iGate Communicating Thermostat Connection to DXM2 Control Thermostat Connection to DXM2 Control Compressor Compressor Stage 2 Reversing...

Страница 30: ...Series IOM 60Hz HFC 410A R ev 3 Au g 2012B DXM2 Wiring Diagram with Internal Flow Controller 96B0005N60 Part 1 of 2 This diagram includes typical wiring details but is not applicable to all units For...

Страница 31: ...31 climatemaster com PRELIMINARY Tranquility 30 Digital TE Series IOM 60Hz HFC 410A Rev 3 Aug 2 0 1 2 B DXM2 Wiring Diagram with Internal Flow Controller 96B0005N60 Part 2 of 2...

Страница 32: ...ies IOM 60Hz HFC 410A R ev 3 Au g 2012B DXM2 Wiring Diagram with Motorized Modulating WaterValve 96B0005N62 Part 1 of 2 This diagram includes typical wiring details but is not applicable to all units...

Страница 33: ...33 climatemaster com PRELIMINARY Tranquility 30 Digital TE Series IOM 60Hz HFC 410A Rev 3 Aug 2 0 1 2 B DXM2 Wiring Diagram with Motorized Modulating WaterValve 96B0005N62 Part 2 of 2...

Страница 34: ...t to engage the Auto Dehumidification feature on units with Internal Flow Controllers Units with Internal Flow Controllers utilize the H terminal on the DXM2 as an input for an ambient temperature swi...

Страница 35: ...0 1100 850 550 1350 Maximum 1500 1100 1200 900 1500 1100 1500 1500 Minimum 900 600 825 550 900 600 450 1350 049 1 0 1 Default 1400 1050 1100 850 1500 1150 700 1500 Maximum 2000 1500 1600 1200 2000 150...

Страница 36: ...he DXM2 AOM is shipped with each unit Thermostat compatibility It is strongly recommended that iGate communicating thermostat ATC32U or iGate configuration diagnostic tool ACDU be used with DXM2 contr...

Страница 37: ...Temp Limit Setting Figure 29 DXM2 Layout and Connections Figure 25 LT1 Limit Setting Comp Relay 24Vdc EH1 EH2 P6 Off On JW3 c1 ay c2 ay CO RV RV LT2 LT2 P7 CC CCG CO S1 S2 12 1 4 Off On AO2 P11 Gnd T...

Страница 38: ...tinuous operating conditions Minimum maximum limits are start up conditions to bring the building space up to occupancy temperatures Units are not designed to operate under these conditions on a regul...

Страница 39: ...y that DXM2 field selection options are properly set Low voltage wiring is complete Blower CFM and Water T is set on communicating thermostats or diagnostic tool Service access panels are in place SYS...

Страница 40: ...eck for warm air delivery at the unit grille within a few minutes after the unit has begun to operate NOTE Units have a five minute time delay in the control circuit that can be bypassed on the DXM2 c...

Страница 41: ...tart up A 10 solution of dishwasher detergent and water is recommended Unit Operating Conditions Table 12 Water Temperature Change Through Heat Exchanger 9 12 20 26 4 8 10 17 Model GPM Pressure Drop p...

Страница 42: ...1 231 197 217 15 20 15 20 15 20 10 15 9 14 9 14 21 9 23 9 16 1 18 1 10 3 12 3 18 24 19 25 19 25 96 106 100 110 105 115 322 342 326 346 331 351 10 15 10 15 10 15 17 22 17 22 17 22 12 2 14 2 9 3 11 3 6...

Страница 43: ...SIG Superheat Subcooling Water Temp Rise F Air Temp Drop F DB Suction Pressure PSIG Discharge Pressure PSIG Superheat Subcooling Water Temp Drop F Air Temp Rise F DB 30 1 5 2 25 3 61 71 65 75 68 78 29...

Страница 44: ...25 3 105 3 61 6 3 6 6 0 1 9 4 4 850 28 1 20 7 1 31 21 4 32 6 80 9 1 9 6 0 1 9 4 4 950 31 7 1 70 5 5 25 9 100 9 61 4 3 5 80 3 0 0 7 1 5 730 24 6 18 0 1 58 15 6 30 0 100 0 3 0 3 0 0 7 1 5 820 31 6 1 76...

Страница 45: ...56 5 5 39 0 111 0 61 3 4 8 9 0 4 4 10 1 1250 43 1 28 8 1 91 22 6 49 6 81 0 2 6 9 0 4 4 10 1 1250 48 5 2 48 5 7 40 0 105 9 61 1 4 7 80 4 5 1 5 3 4 1080 38 0 25 2 2 29 16 6 45 8 100 4 4 3 4 5 1 5 3 4 10...

Страница 46: ...71 4 9 49 1 110 0 61 8 5 2 12 0 3 5 8 1 1550 54 8 39 3 2 55 21 5 63 5 80 6 2 9 12 0 3 5 8 1 1650 62 7 3 59 5 1 50 5 105 2 61 6 5 1 80 6 0 0 8 1 8 1330 47 9 34 6 3 02 15 8 58 2 99 4 4 5 6 0 0 8 1 8 14...

Страница 47: ...73 5 1 66 3 113 6 61 2 6 0 15 0 4 1 9 5 1850 71 1 50 4 3 44 20 6 82 8 81 0 3 5 15 0 4 1 9 5 2050 83 7 4 59 5 3 68 0 107 8 60 9 5 8 80 7 5 0 8 1 8 1590 62 5 44 1 4 05 15 4 76 3 100 3 5 5 7 5 0 8 1 8 1...

Страница 48: ...5 4 5 68 6 116 7 61 9 8 9 17 0 5 4 12 4 1850 77 6 51 5 3 99 19 5 91 2 80 7 5 5 17 0 5 4 12 4 2050 89 5 5 57 4 7 70 5 110 4 61 7 8 7 80 8 5 1 2 2 7 1590 68 4 44 7 4 72 14 5 84 5 99 9 8 2 8 5 1 2 2 7 17...

Страница 49: ...mance Filters should be inspected every month under normal operating conditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic fi...

Страница 50: ...14 8 4 20 116 240 8 0 43 47 116 6 4 04 117 242 6 0 42 48 118 4 3 89 118 244 4 0 41 49 120 2 3 74 119 246 2 0 40 50 122 0 3 60 120 248 0 0 39 51 123 8 3 47 121 249 8 0 38 52 125 6 3 34 122 251 6 0 37 5...

Страница 51: ...s The Control Diagnostics menus allow the installer to see the current status of all DXM2 control switch inputs values of all temperature sensor inputs control voltage ECM blower internal flow center...

Страница 52: ...Start Did Unit Attempt to Start Did Unit Lockout at Start up Unit Short Cycles Only Fan Runs Only Compressor Runs Did unit lockout after a period of operation Does unit operate in cooling Unit is OK S...

Страница 53: ...ity with hydrometer X Improper low temperature setting 30 F vs 10 F Clip LT1 jumper for antifreeze 10 F use X Water t emperature out of range Bring water temp within design parameters X X Bad thermist...

Страница 54: ...check static vs blower table Too much cold vent air bring entering air temp within design parameters No Fault Code Shown X X No compressor operation See Only Fan Operates X X Compressor overload Check...

Страница 55: ...p backfill ground moisture High Head Pressure X Reduced or no air flow Check for dirty air filter and clean or replace in heating Check fan motor operation and airflow restrictions Too high of externa...

Страница 56: ...r Check capacitor X X Thermostat wiring Check thermostat wiring at or DXM2 Put in Test Mode and then jumper Y1 and W1 to R to give call for fan compressor and electric heat Unit Doesn t Operate in Coo...

Страница 57: ...Water to Water units only Temp Diff Temp Diff Water to Water units only Water to Water units only Temp Diff Heating Description Notes Cooling COMPRESSOR DISCHARGE SUCTION HWG AIR COIL EXPANSION VALVE...

Страница 58: ...LW E XQTXDOL HG SHUVRQQHO 0ROG IXQJXV RU EDFWHULD GDPDJHV RUURVLRQ RU DEUDVLRQ RI WKH SURGXFW 3URGXFWV VXSSOLHG E RWKHUV 3URGXFWV ZKLFK KDYH EHHQ RSHUDWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLR...

Страница 59: ...59 climatemaster com PRELIMINARY Tranquility 30 Digital TE Series IOM 60Hz HFC 410A Rev 3 Aug 2 0 1 2 B Notes...

Страница 60: ...limateMaster s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express warrant...

Отзывы: